Character
PV screen
Auxiliary screen
Designation
Description
Initial value
13
ch
Set a control type
Timer connection channel
: Unrelated to the timer
: The timer starts/stops control.
Control operation
: TYPE A
: TYPE B (overshoot inhibition function)
Main output control type
: PID control
: ON/OFF control
: Cascade control (CH2 only)
: Remote control (CH2 and only when the
input type is between and )
Type of auxiliary output control
: Disabled
: PID
: ON/OFF
14
ch
Set forward/
reverse action
switchover
: Reverse action
: Forward action
15
ch
Main output
operation amount
Used to monitor the main output operation amount and
to set the operation amount in manual control.
In automatic control
Display range: 0.0 to 100.0 (-10.0 to -110.0: in analog
output)
Display unit: %
In manual control
Setting range: Lower limit to the upper limit for the
operation amount limiter
Setting unit:
%
16
ch
Set a tuning type
: Auto-tuning (output 1)
: Self-tuning (output 1)
: Auto-tuning (output 2)
: Self-tuning (output 2)
: Auto-tuning (output 1, output 2)
Select // and press the FUNC 1 key to start the
auto-tuning.
Press the FUNC 1 key during the auto-tuning to release
it.
17
ch
Set an AT factor
Setting range: 0.1 to 10.00
Setting unit: Times