150kW InfraStruXure System—Installation and Start-Up

9

Electrical Requirements and Specifications

Procedures requiring a licensed electrician

Electrical requirements

† Provided by customer.

‡The specifications are recommendations. Consult the NEC and local code for requirements specific to your

installation.

Electrical

Hazard

Only a certified electrician can:

• Connect the PDU to its power source

• Connect a switch to the EPO interface on the PDU

• Install a customer-specified, hard-wired power cable

• Perform maintenance of the PDU

480V

600V

Service distribution breaker

†‡

225A

200A

Conductors to Main Input switch

3W + G + GEC

3W + G + GEC

Recommended wire sizing

L1, L2, L3

2/0AWG

2/0AWG

G

6AWG

6AWG

GEC

4AWG 4AWG