beautypg.com

Precooler control, Syntax, Precoolerpid.on[=i – ROTRONIC MBW 373 User Manual

Page 43: Precoolerpid.setpt, Precoolerpid.fixedsetpt[=n, Precoolerpid.deltasetpt[=n, Precoolerpid.fixedon[=i, Precoolerpid.deltaon[=i, Analog outputs, Ana1.param[=i

background image

39

Precooler Control

Syntax Function
PreCoolerPID.on[=i][?]

1

ÆPrecooler On, 0ÆOff

PreCoolerPID.setPt?

Current Precooler temp setpoint, °C

PreCoolerPID.fixedSetPt[=n][?]

Setpoint for fixed mode control, °C

PreCoolerPID.deltaSetPt[=n][?]

Setpoint for delta mode control, °C

PreCoolerPID.fixedOn[=i][?]

1

Æfixed mode control enabled, 0Ædisabled

PreCoolerPID.deltaOn[=i][?]

1

Ædelta mode control enabled, 0Ædisabled

SavePID=373

Save these and other PID parameters

Analog Outputs

See Analog Outputs on page 21 for explanation of the parameters.

Syntax Function
Ana1.param[=i][?]

Parameter to track with analog output #1

Ana1.paramMin[=n][?]

Min Value

Ana1.paramMax[=n][?]

Max Value

Ana1.OutMin[=n][?]

Min Voltage

Ana1.OutMax[=n][?]

Max Voltage

Ana1.calGain[=n][?]

Gain calibration factor for D/A converter

Ana1.calZero[=n][?]

Zero calibration factor for D/A converter

Ana1.output=n

Use to set analog output when calibrating D/A
converter. Automatically sets Ana1.hold=1. You
must send Ana1.hold=0 when finished with
calibration.

Ana1.hold[=i][?]

1

ÆCalibration mode. Analog output is set with the

command Ana1.output=n.
0

ÆNormal mode. Analog output tracks the

parameter set with Ana1.param=i.

SaveCfg=373

Save these and other configuration parameters

Ana2.param[=i][?]

Parameter to track with analog output #2

Ana2.paramMin[=n][?]

Min Value

Ana2.paramMax[=n][?]

Max Value

Ana2.OutMin[=n][?]

Min Voltage

Ana2.OutMax[=n][?]

Max Voltage

Ana2.calGain[=n][?]

Gain calibration factor for D/A converter

Ana2.calZero[=n][?]

Zero calibration factor for D/A converter

Ana2.output=n

Use to set analog output when calibrating D/A
converter. Automatically sets Ana2.hold=1. You
must send Ana2.hold=0 when finished with
calibration.

Ana2.hold[=i][?]

1

ÆCalibration mode. Analog output is set with the

command Ana2.output=n.
0

ÆNormal mode. Analog output tracks the

parameter set with Ana2.param=i.

SaveCfg=373

Save these and other configuration parameters