7 Example telegrams
BU 0070 GB
Subject to technical alterations
33
7.2 Enable with 50% setpoint
A frequency inverter in the "Standby" status must be enabled for clockwise rotation with 50% setpoint. The last
response telegram was received as follows in the controller.
Procedure:
• Check last status word (ZSW 0A 31)
• Generate control word (STW 04 7F)
• Check response telegram (ZSW 0F 37)
Details:
Starting requirement (status word of frequency inverter)
9
10
11 12
ZSW
ZSW
IW1 IW1
0B
31
00 00
The following telegram must be sent to the frequency inverter
9
10
11
12
STW
STW
SW1
SW1
04
7F
20
00
The frequency inverter accelerates the motor in the ramp. When the inverter reaches 50% setpoint, it responds
with the following telegram.
9
10
11 12
ZSW
ZSW
IW1 IW1
0F
37
20 00
Note:
The status of MFR 1 is indicated in Bit 10 of the response telegram. Depending on the programmed
function and status, the status word may differ.
- B1000 (820 pages)
- B2000 (60 pages)
- B1050 (36 pages)
- B2050 (48 pages)
- B1091 (28 pages)
- B1091-1 (28 pages)
- B1092 (52 pages)
- B1901 (6 pages)
- B1904 (23 pages)
- BU0180 (184 pages)
- BU0200 (314 pages)
- BU0210 (60 pages)
- BU0220 (100 pages)
- BU0230 (76 pages)
- BU0240 (40 pages)
- BU0260 (116 pages)
- BU0270 (76 pages)
- BU0280 (78 pages)
- BU0290 (76 pages)
- BU0300 (148 pages)
- BU0310 (8 pages)
- BU0320 (2 pages)
- BU0500 (180 pages)
- BU0505 (188 pages)
- BU0510 (81 pages)
- BU0530 (56 pages)
- BU0540 (64 pages)
- BU0550 (100 pages)
- BU0560 (4 pages)
- BU0570 (44 pages)
- BU0590 (48 pages)
- BU0700 (131 pages)
- BU0701 (1 page)
- BU0710 (32 pages)
- BU0750 (157 pages)
- BU0930 (8 pages)
- BU0940 (44 pages)
- BU2100 (34 pages)
- BU2200 (42 pages)
- MI0300 (36 pages)
- MI0700 (84 pages)
- BU0000 (85 pages)
- BU0010 (4 pages)
- BU0020 (104 pages)
- BU0040 (60 pages)