5 Settings and displays
BU 0070 GB
Subject to technical alterations
17
Parameter
Setting value / Description / Note
Available in Option
P513
Telegram down time
Always visible
0.0 / 0.1 ... 100.0 s
[ 0.0 ]
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one must
arrive within the set period. Otherwise the inverter reports an error and switches off with the error
message E010 >Bus Time Out<.
Monitoring is switched off at a setting value of 0.0.
P543 (P)
Actual bus value 1
Always visible
0 ... 21
[ 1 ]
The return value 1 (IW1) can be set for bus control in this parameter.
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current
5 = Status of digital inputs and relay
6 = Actual position (with PosiCon, SK 700E only)
7 = Setpoint position (with PosiCon, SK 700E only)
8 = Setpoint frequency
9 = Error number
10 = Actual position increment
1
(with PosiCon, SK
700E only)
11 = Actual position increment
1
(with PosiCon, SK
700/750E only)
12 = Bus IO Out Bits 0...7
13 = ... 16 (reserved)
17 = Value analog input 1 (P400)
18 = Value analog input 2 (P405)
19 = Setpoint frequency master value (P507)
20 = Setpoint frequency after master value ramp
21 = Setpoint frequency without master value slip
P544 (P)
Actual bus value 2
Always visible
0 ... 21
[ 0 ]
The return value 2 (IW2) can be set for bus control in this parameter.
This parameter is identical to P543.
Condition is PPO 2 or PPO 4 type (P507).
P545 (P)
Actual bus value 3
Always visible
0 ... 21
[ 0 ]
The return value 3 (IW3) can be set for bus control in this parameter. This is only available if P546 is
≠
3 (not with SK 5xxE).
This parameter is identical to P543.
Condition is PPO 2 or PPO 4 type (P507).
P546 (P)
Bus setpoint 1
Always visible
0 ... 6
[ 1 ]
valid for
SK 300/700/750E
In this parameter, a function is assigned to the delivered setpoint 1 (SW1) for bus control.
0 = Off
1 = Setpoint frequency (16 Bit)
2 = 16-bit setpoint position (with PosiCon option only)
3 = 32-bit setpoint position (only available with PosiCon option and when PPO type 2 or 4 is selected)
4 = PosiCon control terminals (only available with PosiCon option, 16-bit)
5 = Setpoint position (16 Bit) increment
1
(with PosiCon, SK 700E only)
6 = Setpoint position (32 Bit) increment
1
(with PosiCon, SK 700E only)
1
The setpoint/actual position corresponding to an 8192 increment encoder.