NORD Drivesystems BU0070 User Manual
Page 24

NORDAC InterBus Operating Manual
24
Subject to technical alterations
BU 0070 GB
6.1.2 The status word (ZSW)
The status word (ZSW) is the first word transferred to the inverter in the process data area in the inverter response
telegram.
PZD1 PZD2 PZD3 PZD3
ZSW IW1 IW3 IW2
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Significance of the individual bits
Bit
Value
Significance
Comments
0
0
Not on standby
1
Standby
Initialisation complete, load relay on, output voltage blocked
1
0
Not operational
Causes: No On command, an error has occurred, OFF 2 or OFF 3
active, switch-on block status active.
1
Ready for operation
On command active, no errors. The inverter can be started with the
ENABLE OPERATION command.
2 0
Operation
blocked
1
Operation enabled
Output voltage enabled, run-up to present setpoint.
3 0
No
errors
1
Error
Drive malfunctioning therefore out of order, if acknowledgement is
successful, will go to switch-on block status.
4
0
OFF 2
OFF 2 command active
1
No OFF 2
5
0
OFF 3
OFF 3 command active
1
No OFF 3
6
0
No switch-on block
1
Switch-on block
Goes through OUT 1 to Standby status
7 0
No
warning
1
Warning
Drive still in operation, no acknowledgement necessary
8
0
Actual value not O.K.
Actual value does not match the setpoint (with posicon: Setpoint
position not reached)
1
Actual value O.K.
Actual value matches the setpoint (setpoint reached)
(with posicon: Setpoint position reached)
9
0
Local guidance
Local guidance active on device
1
Guidance required
The Master is called upon to take over the guidance.
10
0
MFR 1 reference value
undershot
Programmed function of the MFR 1 not met or
actual value < programmed reference value
1
MFR 1 reference value
reached
Programmed function of the MFR 1 met or
actual value > programmed reference value
11 0
1
Rotation right
Inverter output voltage has right-hand rotating field
12 0
1
Rotation left
Inverter output voltage has left-hand rotating field
13
0
MFR 4 reference value
undershot
For SK 700E only with posicon upgrade: status MFR 4 = 0
1
MFR 4 reference value
reached
For SK 700E only with posicon upgrade: status MFR 4 = 1
14 0/1
Actual
active
parameter
set Bit 0
00 Parameter set 1
01 Parameter set 2
10 Parameter set 3
11 Parameter set 4
15 0/1
Actual
active
parameter
set Bit 1