4 the interbus protocol, 1 drive profile, 2 data length – NORD Drivesystems BU0070 User Manual

Page 13: 1 ppo type 1, 2 ppo type 2

background image

4 The InterBus protocol

BU 0070 GB

Subject to technical alterations

13

4 The InterBus protocol


InterBus works with a summation frame protocol. Each subscriber has a fixed data length.

Note:

If the mode switch is permanently set (Position 1 – 3), the software/parameter settings are ineffective!

4.1 Drive profile

If the drive is to be operated as per DRIVECOM 21 profile, the frequency inverter can be configured via Parameter
551. This also changes the ID of the subscriber.
Drive profile On (P551 = 1)

ID[7..0]= E3h

Æ DRIVECOM with 1 PCP word, RemoteBus

Drive profile Off (P551 = 0)

ID[7..0]= F3h

Æ Module with 1 PCP word, RemoteBus

To render the profile change effective, the module must be reinstalled (e.g. switch the mains voltage off
and then on again). The entire bus must also be restarted. The profile is only effective with 3 word data
lengths (PPO type 1).


4.2 Data length

The default setting is 5 words when the inverter is switched off.
Attention: After the frequency inverter is switched on, the profile and PPO type settings are read in and
the InterBus reinitialised (P507 and P551).



The data length can be set between 3 and 5 words for the IBS module and is set via the PPO types (P507: see
Chap. 5.1). The PPO types 3 and 4 are reserved.


To render the data length change effective, the InterBus must be reinstalled (e.g. switch the mains voltage
off and then on again). The entire bus must also be restarted.

4.2.1 PPO type 1

3 words data width
Drive profile On (P551 = 1)

ID[7..0]= E3h

Æ DRIVECOM with 1 PCP word, RemoteBus

Drive profile Off (P551 = 0)

ID[7..0]= F3h

Æ Module with 1 PCP word, RemoteBus











4.2.2 PPO type 2

5 words data width
ID[7..0]= F3h

Æ Module with 1 PCP word, RemoteBus

Note: The parameter "Drive profile" has no effect.








0

Control word

Status word

1

Speed setpoint

(rpm

)

Speed actual

value (rpm)

PCP

PCP

out

in

2

3

4

5

Byte

0

Control word

Status word

1

PCP

PCP

out

in

2

3

Byte

Setpoint 1

Act. value 1

4

5

Setpoint 3

Act. value 3

6

7

Setpoint 2

Act. value 2

8

9