2 field bus customer units, Field bus customer units – NORD Drivesystems MI0700 User Manual
Page 60
Frequency inverters
– Migration Guide SK 700E to SK 5xxE
60
MI 0700 GB-0414
Pos : 62 /Migrati onsl eitf aden/ SK 700E - SK 500E/3. Leis tungs- und Steuer klemmenansc hluss /3.2.2 Fel dbus Kundens chnitts tell en @ 3\ mod_1366286396375_388. doc x @ 64041 @ 3 @ 1
3.2.2 Field bus customer units
To connect field bus systems (incl. some I/O control signal terminals) to the SK 700E frequency
inverters, 4 different field bus customer units are offered. In contrast, the SK 5xxE series of frequency
inverters by default comes with respective onboard terminals to connect some field bus systems and
some I/O control signals. Please heed the differing terminal numbers/terminal names (e.g.
terminal 42 / VO 15V, terminal 44 / VI 24V or VO 24V) for the different power supplies of inputs and
outputs of the SK 5xxE frequency inverter types or sizes.
SK 700E
Name
Function
[factory setting]
SK 5xxE
Customer unit
SK CU1-PBR
Part No.
Connector
Terminal No.
Name
Terminal strip
Terminal No.
Name
SK 5xxE
onboard
Part No.
PROFIBUS DP
SK CU1-PBR
X6.1
01
REL1.1
Relay 1 / output 1
NO relay contact
[brake control
{1}
]
X3
1
K1.1
X3
02
REL1.2
2
K1.2
X6.2
42
VO + 15V
15 V supply voltage
X5
42*
44*
VO 15V
VI 24V
VO 24V
X5
21
DIG IN 1
digital input 1
[release right {1}]
21
DIN1
41
VO +5V
5 V supply voltage
41
VO 5V
40
GND / 0V
0 V digital
40
GND/0V
X6.3
47
PBR +5V
PBR 5 V supply
voltage
SUB
D9
s
o
c
k
e
t
PIN 6
+5 V
SK TU3-PBR
technology unit
Part No.
48
PBR 0V
PBR 0 V supply
voltage
PIN 5
GND
278200030
81
PBR A
PROFIBUS DP
BUS + (
green
wire)
RxD/TxD-P
PIN 8
A data
PROFIBUS DP
SK TU3-PBR **
275900030
82
PBR B
PROFIBUS DP
BUS - (red wire)
RxD/TxD-N
PIN 3
B data
83
PBR RTS
PROFIBUS DP
Ready to send
PIN 4
RTS
X6.4
81
PBR A
PROFIBUS DP
BUS + (
green
wire)
RxD/TxD-P
PE separately
via cable lug
82
PBR B
PROFIBUS DP
BUS - (red wire)
RxD/TxD-N
90
SHIELD
PROFIBUS DP