Table 3: overview of frequency inverter functions, Information, 1 introduction – NORD Drivesystems MI0700 User Manual
Page 13: Integrated mains filter
1 Introduction
MI 0700 GB-0414
13
SK 700E
Performance levels
SK 5xxE
Name
Name
SK 700E-xxx-340-X (-RS2) *
+ CAN Bus
SK CU1-CAN-RJ
1.5
kW … 7.5 kW / 2 hp … 10 hp
SK 511E-xxx-340-A
11.0
kW … 160.0 KW / 15 hp … 220 hp
SK 515E-xxx-340-A
SK 700E-xxx-340-X (-RS2) *
+ CAN Bus
SK TU1-CAN
1.5
kW … 7.5 kW / 2 hp … 10 hp
SK 511E-xxx-340-A
optional
WAGO-
adapter module
RJ45/terminal ****
11.0
kW … 160.0 KW / 15 hp … 220 hp
SK 515E-xxx-340-A
optional
WAGO-
adapter module
RJ45/terminal ****
SK 700E-xxx-340-X (-RS2) *
+ CANopen Bus
SK TU1-CAO
1.5
kW … 7.5 kW / 2 hp … 10 hp
SK 511E-xxx-340-A
+ CANopen Bus
SK TU3-CAO
11.0
kW … 160.0 KW / 15 hp … 220 hp
SK 515E-xxx-340-A
+ CANopen Bus
SK TU3-CAO
*
(-RS2) with additional optional/integrated RS232 interface on SK
700E frequency inverters ≤ 22.0 kW.
The token X represents A (with integrated mains filter) on SK
700E frequency inverters ≤ 22.0 kW
O (without integrated mains filter) on SK
700E frequency inverters ≥ 30.0 kW
**
plus one of the customer units SK CU1-BSC, SK CU1-STD, SK CU1-MLT or SK CU1-MLT-20mA.
***
When a great number of control signals (number of used DIs and DOs of customer units SK CU1-xxx and extension
units SK XU1-POS) for the SK 700E and the available DIs and DAs of the SK 5xxE are used, an additional IO
extension type SK EBIOE-2 (275900210) is necessary. The IO extension Scan only be connected to SK 540E and
SK 545E frequency inverters.
****
WAGO adapter module RJ45/terminal (278910300) to connect the CAN cable with an RJ45 western plug to the
SK 5xxE, alternatively crimp an RJ45 plug to the CAN cable.
Table 3: Overview of frequency inverter functions
Information
Integrated mains filter
The SK 700E frequency inverters of power range 1.5 kW to 22.0 kW listed above come with an integrated mains
filter of class A by default and are identified with abbreviation -A in the type code. SK 700E frequency inverters
with a power ≥30.0 kW do not feature an integrated mains filter and are identified with abbreviation -O in the type
code. All SK 5xxE frequency inverters (complete power range from 1.5 kW to 160 kW) come ex factory with an
integrated Class C2 (industrial) mains filter. With motor cable lengths ≤ 5 m, the SK 5xxE frequency inverters in
the power range 1.5 kW to 7.5 kW even comply with Class C1 (residential and industrial). All SK 5xxE frequency
inverters feature an on board integrated mains filter and are identified with abbreviation -A in the type code.
For information on the mains filter functions of SK 700E-
…-A or … -O frequency inverters with and without
integrated mains filter, please refer to the respective manual (BU 0700)
(www.nord.com)
.