To connect I/O control signals to the SK 700E frequency inverters, 6 different I/O customer units are
offered. In contrast, the SK 5xxE series of frequency inverters by default comes with respective
onboard terminals to connect the I/O control signals. Please heed the differing terminal
numbers/terminal names (e.g. terminal 42 / VO 15V, terminal 44 / VI 24V or VO 24V) for the different
power supplies of inputs and outputs of the SK 5xxE frequency inverter types or sizes.
SK 700E
Name
Function
[factory setting]
SK 5xxE
Customer unit
SK CU1-BSC
Part No.
Connector
Terminal No.
Name
Terminal strip
Terminal No.
Name
SK 5xxE
onboard
Part No.
Basic I/O
SK CU1-BSC
X3.1
01
REL1.1
Relay 1 / output 1
NO relay contact
[brake control
{1}
]
X3
1
K1.1
X3
02
REL1.2
2
K1.2
X3.2
11
VREF 10V
10 V reference voltage
X4
11
VO 10V
12
AGND/0V
0 V analogue
12
GND/0V
X4
13
AIN1 -
analogue input 1 -
12
GND/0V
14
AIN1 +
analogue input 1 +
[setpoint frequency {1}]
14
AIN1
278200000
X3.3
21
DIG IN 1
digital input 1
[release right {1}]
X5
21
DIN1
X5
275xxxxxx
22
DIG IN 2
digital input 2
[release left {2}]
22
DIN2
23
DIG IN 3
digital input 3
[Par. record switchover
{8}]
23
DIN3
42
VO + 15V
15 V supply voltage
42*
44*
VO 15V
VI 24V
VO 24V
*
Depending on the frequency inverter types and sizes, the supply voltages, terminal numbers or terminal names differ.
Terminal X5: 42 / VO 15V for SK 500E, SK 510E, SK 511E, SK 520E, SK 530E and SK 540E, all sizes 1 - 4
Terminal X5: 44 / VI 24V for SK 505E, SK 515E, SK 535E and SK 545E, all sizes 1 - 4, VI 24V is mandatory for 24 V supply
of the digital inputs and the control unit of the frequency inverter. This terminal is also available on terminal block X7, X12
and X15.
Terminal X5: 44 / VO 24V for SK 505E, SK 515E, SK 535E and SK
545E, ≥ size 5, VO 24V is available as 24 V output
voltage for supplying the digital inputs. This terminal is also available on terminal block X7.
For more information, refer to manuals BU 0500 or BU 0505 (se
Table 34: Customer unit Basic I/O, SK CU1-BSC
Information
Analogue input (differential input)
When using the analogue input of the Basic I/O SK CU1-BSC customer unit , implemented as differential input, it
must be taken into consideration that the SK 5xxE frequency inverters only feature non-isolated analogue inputs!
This also applies to the basic I/O of type SK CU1-STD for SK 700E frequency inverters.