10.5 Data for the safe pulse block

(only for SK 210E, SK 215E, SK 230E and SK 235E)

Function

Specification

Input voltage

+24 V

Voltage tolerance

±25 % (18

V…30 V)

Operation at OSSD

-

20 % +25 % (19.2 V…30 V)

Power consumption

(mean value)

≤ 125 mA for SK 2xxE in Size 1 to 3

≤ 40 mA

for SK 2x0E in Size 4

Peak current

(peak, when switching on or at the
OSSD)

≤ 500 mA for SK 2xxE in Size 1 to 3

≤ 250 mA for SK 2x0E in Size 4

Cable length

≤ 100 m (refer to EMC, grouping)

Line capacitance

≤ 20 nF per connected inverter

Switch-on delay

≤ 200 ms

Reaction time

≤ 300 ms (≤ 65 ms typical)

Cycle time

≥ 1 s

Requirements made of OSSDs

Test pulse width ≤ 500 µs

Duty (high level) ≥ 90 %

Distance between double pulses ≥1ms (note the duty factor)

Safety integrity level (IEC 61508)

SIL3

Probability of a hazardous failure per
hour

PFH = 0

for SK 2xxE in Size 1 to 3

PFH = 0.0058 FIT = 5.8*10

-12

/h

for SK 2xxE in Size 4

Probability of a hazardous failure on
call-up

PFD = 0

for SK 2xxE in Size 1 to 3

PFD = 5.23*10

-5

for SK 2xxE in Size 4

Proportion of safe failures

SFF = 100 % for SK 2xxE in Size 1 to 3

SFF = 99 %

for SK 2xxE in Size 4

Safety category

(as per to EN ISO 13849-1)

Cat. 4

Performance level
(as per to EN 13849-1)

PL e

The mean time until a hazardous
failure

MTTF

d

= "High" (>100 years)

Diagnostic coverage level

DC cannot be determined (PFH=0) for SK 2xxE in Size 1 to 3

DC > 99 %

for SK 2xxE in Size 4

Lifetime

TM = 20 years