5 data for the safe pulse block – NORD Drivesystems BU0230 User Manual
Page 72
Functional safety with NORD SK 200E frequency inverters
72
BU 0230 GB-2712
10.5 Data for the safe pulse block
(only for SK 210E, SK 215E, SK 230E and SK 235E)
Function
Specification
Input voltage
+24 V
Voltage tolerance
±25 % (18
V…30 V)
Operation at OSSD
-
20 % +25 % (19.2 V…30 V)
Power consumption
(mean value)
≤ 125 mA for SK 2xxE in Size 1 to 3
≤ 40 mA
for SK 2x0E in Size 4
Peak current
(peak, when switching on or at the
OSSD)
≤ 500 mA for SK 2xxE in Size 1 to 3
≤ 250 mA for SK 2x0E in Size 4
Cable length
≤ 100 m (refer to EMC, grouping)
Line capacitance
≤ 20 nF per connected inverter
Switch-on delay
≤ 200 ms
Reaction time
≤ 300 ms (≤ 65 ms typical)
Cycle time
≥ 1 s
Requirements made of OSSDs
Test pulse width ≤ 500 µs
Duty (high level) ≥ 90 %
Distance between double pulses ≥1ms (note the duty factor)
Safety integrity level (IEC 61508)
SIL3
Probability of a hazardous failure per
hour
PFH = 0
for SK 2xxE in Size 1 to 3
PFH = 0.0058 FIT = 5.8*10
-12
/h
for SK 2xxE in Size 4
Probability of a hazardous failure on
call-up
PFD = 0
for SK 2xxE in Size 1 to 3
PFD = 5.23*10
-5
for SK 2xxE in Size 4
Proportion of safe failures
SFF = 100 % for SK 2xxE in Size 1 to 3
SFF = 99 %
for SK 2xxE in Size 4
Safety category
(as per to EN ISO 13849-1)
Cat. 4
Performance level
(as per to EN 13849-1)
PL e
The mean time until a hazardous
failure
MTTF
d
= "High" (>100 years)
Diagnostic coverage level
DC cannot be determined (PFH=0) for SK 2xxE in Size 1 to 3
DC > 99 %
for SK 2xxE in Size 4
Lifetime
TM = 20 years