beautypg.com

NORD Drivesystems BU0230 User Manual

Page 56

background image

Functional safety with NORD SK 200E frequency inverters

56

BU 0230 GB-2712

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P708

Status of digital inputs

00000 ... 11111
(binary)

or

0000 ... FFFF

(hex)

(hexadecimal)

Displays the status of the digital inputs in binary/hexadecimal code. This display can be used to
check the input signals.

Bit 0 = Digital input 1

Bit 1 = Digital input 2

Bit 2 = Digital input 3

Bit 3 = Digital input 4

Bit 4 = Thermistor input

Bits 5 - 7 reserved

First SK xU4-IOE (optional)
Bit 8 = 1st IO extension: Digital input 1
Bit 9 = 1st IO extension: Digital input 2
Bit 10 = 1st IO extension: Digital input 3
Bit 11 = 1st IO extension: Digital input 4

Second SK xU4-IOE (optional)
Bit 12 =
2nd IO extension: Digital input 1
Bit 13 = 2nd IO extension: Digital input 2
Bit 14 = 2nd IO extension: Digital input 3
Bit 15 = 2nd IO extension: Digital input 4

Bits 15-12

Bits 11-8

Bits 7-4

Bits 3-0

Minimum value

0000

0

0000

0

0000

0

0000

0

Binary

hex

Maximum value

1111

F

1111

F

1111

F

1111

F

Binary

hex

SimpleBox: The binary bits are converted to a hexadecimal value and displayed.

ParameterBox: The bits are displayed with increasing values from right to left (binary).

P711

Output status

00000 ... 11111

(bin)

or

00 ... FF

(hex)

Displays the current status of the digital outputs.

Bit 0 = Digital output 1
Bit 1 = mechanical brake
Bit 2 = Digital output 2
Bit 3 = reserved

Bit 4 = Digital output 1, IO extension 1
Bit 5 = Digital output 2, IO extension 1
Bit 6 = Digital output 1, IO extension 2
Bit 7 = Digital output 2, IO extension 2

Bits 7-4

Bits 3-0

Minimum value

0000

0

0000

0

Binary

hex

Maximum value

1111

F

1111

F

Binary

hex

SimpleBox: The binary bits are converted to a hexadecimal value and displayed.

ParameterBox: The bits are displayed with increasing values from right to left (binary).