NORD Drivesystems BU0230 User Manual
Page 56
Functional safety with NORD SK 200E frequency inverters
56
BU 0230 GB-2712
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P708
Status of digital inputs
00000 ... 11111
(binary)
or
0000 ... FFFF
(hex)
(hexadecimal)
Displays the status of the digital inputs in binary/hexadecimal code. This display can be used to
check the input signals.
Bit 0 = Digital input 1
Bit 1 = Digital input 2
Bit 2 = Digital input 3
Bit 3 = Digital input 4
Bit 4 = Thermistor input
Bits 5 - 7 reserved
First SK xU4-IOE (optional)
Bit 8 = 1st IO extension: Digital input 1
Bit 9 = 1st IO extension: Digital input 2
Bit 10 = 1st IO extension: Digital input 3
Bit 11 = 1st IO extension: Digital input 4
Second SK xU4-IOE (optional)
Bit 12 = 2nd IO extension: Digital input 1
Bit 13 = 2nd IO extension: Digital input 2
Bit 14 = 2nd IO extension: Digital input 3
Bit 15 = 2nd IO extension: Digital input 4
Bits 15-12
Bits 11-8
Bits 7-4
Bits 3-0
Minimum value
0000
0
0000
0
0000
0
0000
0
Binary
hex
Maximum value
1111
F
1111
F
1111
F
1111
F
Binary
hex
SimpleBox: The binary bits are converted to a hexadecimal value and displayed.
ParameterBox: The bits are displayed with increasing values from right to left (binary).
P711
Output status
00000 ... 11111
(bin)
or
00 ... FF
(hex)
Displays the current status of the digital outputs.
Bit 0 = Digital output 1
Bit 1 = mechanical brake
Bit 2 = Digital output 2
Bit 3 = reserved
Bit 4 = Digital output 1, IO extension 1
Bit 5 = Digital output 2, IO extension 1
Bit 6 = Digital output 1, IO extension 2
Bit 7 = Digital output 2, IO extension 2
Bits 7-4
Bits 3-0
Minimum value
0000
0
0000
0
Binary
hex
Maximum value
1111
F
1111
F
Binary
hex
SimpleBox: The binary bits are converted to a hexadecimal value and displayed.
ParameterBox: The bits are displayed with increasing values from right to left (binary).