beautypg.com

4 iso 13849-1:2006 – NORD Drivesystems BU0230 User Manual

Page 61

background image

6 Safety categories

BU 0230 GB-2712

61

6.4 ISO 13849-1:2006

(German version EN ISO 13849-1:2008)

For the safety-relevant stop functions STO and SS1 (designation as per IEC 61800-5-2:2007), frequency
inverters with the safe shut-down methods "safe pulse block" and "switch-off of the 24 V supply" fulfil the
requirements for Performance Level e. This ensures that safety category 4 can be achieved.

Shut-down
method

“Safe pulse block”

“Safe pulse block”

"Switch-off of the 24V supply"

Size

Size 1 to 3

Size 4

Size 1 to 3 (SK 205E and SK 215E)

PL

e

e

e

DC

cannot be established
(PFH=0)

"high" (>99%)

cannot be established (PFH=0)

MTTF

d

"high" (>100 years)

"high" (>100 years)

"high" (>100 years)

T

M

20 years

20 years

5 years

Category

4

4

4

PL

Performance Level

DC

Diagnostic coverage level

MTTF

d

Mean time before hazardous failure

T

M

Duration of use

The digital inputs which are used for the implementation of safety-relevant stop functions are primarily intended
as auxiliary inputs and can fulfil the requirements of Safety Category 1 and Performance Level c.

Input

DIN 1 and DIN 4

DIN 2 and DIN 3

PL

c

c

DC

No DC

No DC

PFH

786.69 FIT for SK 2x0E Size 1 to 3
811.98 FIT for SK 2x0E Size 4
811.82 FIT for SK 2x5E Size 1 to 3

789.25 FIT for SK 2x0E Size 1 to 3
814.55 FIT for SK 2x0E Size 4
814.39 FIT for SK 2x5E Size 1 to 3

MTTF

d

"high" (>100 years)

"high" (>100 years)

T

M

20 years

20 years

Category

1

1

NOTE

The values given only refer to the stated inputs or shut-down methods

The components which are additionally required for the implementation of a safety
function, such as a protective switching device, an emergency stop button etc. must also
be taken into account for the evaluation of the safety function. The resulting safety-relevant
data can be significantly influenced by these components.