4 iso 13849-1:2006 – NORD Drivesystems BU0230 User Manual
Page 61
6 Safety categories
BU 0230 GB-2712
61
6.4 ISO 13849-1:2006
(German version EN ISO 13849-1:2008)
For the safety-relevant stop functions STO and SS1 (designation as per IEC 61800-5-2:2007), frequency
inverters with the safe shut-down methods "safe pulse block" and "switch-off of the 24 V supply" fulfil the
requirements for Performance Level e. This ensures that safety category 4 can be achieved.
Shut-down
method
“Safe pulse block”
“Safe pulse block”
"Switch-off of the 24V supply"
Size
Size 1 to 3
Size 4
Size 1 to 3 (SK 205E and SK 215E)
PL
e
e
e
DC
cannot be established
(PFH=0)
"high" (>99%)
cannot be established (PFH=0)
MTTF
d
"high" (>100 years)
"high" (>100 years)
"high" (>100 years)
T
M
20 years
20 years
5 years
Category
4
4
4
PL
Performance Level
DC
Diagnostic coverage level
MTTF
d
Mean time before hazardous failure
T
M
Duration of use
The digital inputs which are used for the implementation of safety-relevant stop functions are primarily intended
as auxiliary inputs and can fulfil the requirements of Safety Category 1 and Performance Level c.
Input
DIN 1 and DIN 4
DIN 2 and DIN 3
PL
c
c
DC
No DC
No DC
PFH
786.69 FIT for SK 2x0E Size 1 to 3
811.98 FIT for SK 2x0E Size 4
811.82 FIT for SK 2x5E Size 1 to 3
789.25 FIT for SK 2x0E Size 1 to 3
814.55 FIT for SK 2x0E Size 4
814.39 FIT for SK 2x5E Size 1 to 3
MTTF
d
"high" (>100 years)
"high" (>100 years)
T
M
20 years
20 years
Category
1
1
NOTE
The values given only refer to the stated inputs or shut-down methods
The components which are additionally required for the implementation of a safety
function, such as a protective switching device, an emergency stop button etc. must also
be taken into account for the evaluation of the safety function. The resulting safety-relevant
data can be significantly influenced by these components.