Functional safety with NORD SK 200E frequency inverters

48

BU 0230 GB-2712

3.8 Digital outputs

The digital output can be used to indicate the status of the "safe pulse block". It should be noted that this status
indication is not fail-safe.

Terminal/

Name

Function

[factory setting]

Data

Description / wiring suggestion

Parameter


SK 200E, SK 210E, SK 220E, SK 230E

1

DO1

Output 1

[Fault]

Digital output (24V)

max. 20 mA (Size 1 to 3)

max. 50 mA (Size 4)

max. 100 k

load

For evaluation in a control system.

P434 [-01]

3

DO2

Output 2

[Fault]

P434 [-02]


SK 205E, SK 215E, SK 225E, SK 235E

1

DO1

Output 1

[Fault]

Digital output

18-30 V, each to VI 24V

max. 200 mA

max. 100 k

load

For evaluation in a control system.

With SK 225/235E and use of the
AS-i (yellow cable), DO1 must not
be subjected to load, as the load
may be too high for the AS-i.

In the inverter is supplied by a 24V
module on terminals 44 (+24V) and
40 (GND), SK CU4-24V-123-B or
SK CU4-24V-140-B, the digital
output may only have a load of
maximum 150 mA.

P434 [-01]

If "switch-off of the 24V supply" is selected as the safe shut-down method, the digital output may not be able to
be meaningfully used, as it is switched off with the 24 V supply. It must be ensured that no external voltage is
introduced via the digital output.