7 Commissioning

Only the requirements for functional safety will be dealt with here. A detailed section regarding the
commissioning of the standard functions of the SK 200E frequency inverter can be found in the manual BU
0200 GB.

ATTENTION

DANGER TO LIFE!

The frequency inverter is not equipped with a line main switch and is therefore always live when
connected to the power supply. Live voltages may therefore be connected to a connected motor
at standstill.

For the implementation of a safety function (STO or SS1), in addition to a safe shut-down method, a digital
input is used, which should be assigned a special function. Because of this, when commissioning, a PC with
an RS232/458 interface, or alternatively a SimpleBox/ParameterBox is required for parameterisation.

Configuration by means of the DIP switches alone is not possible!

Care must be taken that the DIP switches "I/O" (S1:4 and S1:5) are in the position "0" ("off"). It is only in this
position that the digital inputs can be assigned the function "Disable Voltage" [10] or "Fast Stop" [11] via the
parameters P420 [-

01]…[-04] (see Section "Parameterisation").

No.

Bit

DIP switch (S1)

8

2

7

Int R

Brake

Internal brake
resistor

0

Behaviour corresponding to P555, P556, P557

1

Behaviour corresponding to the brake resistor
used

7

2

6

60Hz*

50/60Hz-operation

0

Motor data corresponding to the rated power of the
FI in kW relative to 50Hz, fmax = 50Hz

1

Motor data corresponding to the rated power of the
FI in hp relative to 60Hz, fmax = 60Hz

6

2

5

V/F

Regulating
process

0

VFC regulation corresponding to P211/P212

1

V/f curve (

P211=0 and P212=0)

5/4

2

4/3

I/O

Potentiometer
function, digital
inputs and AS
interface

DIP-No

5

4

0

0

Corresponding to P420 [1-4] and P400 [1-2]
or P480 [1-4] and P481 [1-4]

0

1

Further

details

in

the

next

table.

(depends on the DIP3 "BUS")

1

0

1

1

3

2

2

BUS

Source control
word and setpoint
value

0

Corresponding to P509 and P510 [1] [2]

1

System bus (

P509=3 and P510=3)

2/1

2

1/0

ADR

System bus
address/ baud rate

DIP-No

2

1

0

0

Corresponding to P515 and P514
[32, 250kBaud]

0

1

Address 34, 250kBaud

1

0

Address 36, 250kBaud

1

1

Address 38, 250kBaud

*) A changed setting is applied the next time the mains is switched on.

Existing settings in parameters P201-P209 and P105 are overwritten!