1 General information


BU 0210 GB

Subject to technical amendments

9

1.2 Certifications

1.2.1

European EMC Directive

If the NORDAC SK 200E is installed according to the recommendations in this
instruction manual, it meets all EMC directive requirements, as per the EMC
product standard for motor-operated systems EN 61800-3. (see also Section
8.1, Electromagnetic Compatibility [EMC].)


1.2.2

UL Approval - File No. E171342 (in preparation)

“Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical Amperes, 120 Volts maximum (SK2xxE-xxx-112), or -240 Volts
maximum (SK2xxE-xxx-323), or 500 Volts maximum (SK2xxE-xxx-340) and
when protected by J class fuses as indicated.”

Suitable for use with mains with a maximum short circuit current of 5000A (symmetrical), 120V maximum (SK
2xxE-xxx-112), 240V maximum (SK 2xxE-xxx-323), or 500V maximum (SK 2xxE-xxx-340), and with protection
with a J-class fuse as described in BU 0200 GB Section 7.7.
SK 200E frequency inverters include a motor overload protection. Further technical details can be found in
Section 7.7 of BU0200


1.2.3

C-Tick labeling

NORD SK 200E series frequency inverters fulfil all the relevant regulations in
Australia in New Zealand.


1.2.4

RoHS compliance

SK 200E series frequency inverters are designed to be RoHS compliant
according to Directive 2002/95/EEC


N 23134