4 Parameter settings


BU 0210 GB

Subject to technical amendments

31

4 Parameter settings


For a detailed overview of all available parameters, please refer to Manual SK 2x5E, BU0200 The following
only lists selected parameters and parameters specific to the function of PosiCon.

Operating display:

Parameters
[factory setting]

Setting value / Description / Note

Device

Supervisor

Parameter set

P001

Selection display

0 ... 63

[ 0 ]

Caution:

Only the functions relevant to PosiCon are listed here.

16 = Position setpoint

17 = Actual position

50 = Actual position increments.

Actual position value of the incremental encoder

51 = Absolute actual position

.

Actual position of the absolute encoder

52 = Actual position difference.

Actual position difference

53 = Actual position difference abs/inc

Actual position difference (P631) between absolute

encoder and incremental encoder

54 = Actual position difference calc/measured

Actual position difference (P630) between the calculated

and measured difference of an encoder

Control parameters:

Only available in SK 2x5E with the use of an incremental encoder. For connections, please see Section 2.1.1
Colour and contact assignments for the incremental encoders.

Parameters
[factory setting]

Setting value / Description / Note

Device

Supervisor

Parameter set

P300

Servo mode

P

0 ... 1

[ 0 ]

This parameter activates speed control with speed measurement via an incremental encoder.
This leads to a very stable speed behaviour down to motor standstill.

0 = Off

1 = On

NOTE:

For correct function, an incremental encoder must be connected (see control

connections, Section 2.1 Incremental encoder connection ) and the correct pulse
number must be entered in parameter P301.

P301

Incremental encoder pulse number

0 ... 17

[ 6 ]

Input of the pulse-count per rotation of the connected incremental encoder.

Corresponds to the direction of rotation of the encoder -not that of the frequency inverter
(depending on installation and wiring), this can be compensated for by selecting the
corresponding negative pulse numbers 8..to.16.

0 = 500 pulses
1 = 512 pulses
2 = 1000 pulses
3 = 1024 pulses
4 = 2000 pulses
5 = 2048 pulses
6 = 4096 pulses
7 = 5000 pulses

17 =

8192 pulses

8 = -500 pulses
9 = -512 pulses

10 = -1000 pulses
11 = - 1024 pulses
12 = - 2000 pulses
13 = -2048 pulses
14 = -4096 pulses
15 = -5000 pulses

16 = -8192 pulses