SK 2x5E with "PosiCon Functionality"

36

Subject to technical amendments

BU 0210 GB

Parameter
[factory setting]

Setting value / Description / Note

Device

Supervisor

Parameter
set

P546

[-

01]

...
[-

03]

Function Bus setpoint 1 ... 3

S

P

0 ... 24

[ -01 = 1 ]

[ -02 = 0 ]

[ -03 = 0 ]

In this parameter, a function is allocated to the output setpoint during bus actuation.

NOTE:

For further details please refer to the relevant Bus Manual BU 0250 or the
description for P400.

[-01] = Bus setpoint value 1

[-02] = Setpoint bus value 2

(only for PPO Type 2 or 4)

[-03] = Setpoint bus value 3

(only for PPO Type 2 or 4)

Possible values which can be set:

20 =

Bus IO In Bits 0…7

21 =

Setpoint position Low-word

22 =

Setpoint position High-word

23 =

Setpoint position in incremental Low-word

24 =

Setpoint position in incremental High-word

P552

[-01]


[-02]

System bus master cycle time

S

0 / 0.1 … 100.0 ms

[ 0 ]

In this parameter, the cycle time for the system bus master mode and the CAN open
encoder is set (see P503/514/515):

[01] =

Cycle time for system bus master functions

[02] =

Cycle time for system absolute value encoder

With the setting 0 = "Auto" the default value (see table) is used.

According to the Baud rate set, there are different minimum values for the actual cycle time:

Baudrate

Minimum value t

Z

Default system bus master

Default system bus abs.

10kBaud 10ms

50ms

20ms

20kBaud 10ms

25ms

20ms

50kBaud 5ms

10ms

10ms

100kBaud 2ms

5ms

5ms

125kBaud 2ms

5ms

5ms

250kBaud 1ms

5ms

2ms

500kBaud 1ms

5ms

2ms

1000kBaud 1ms

5ms

2ms

NOTE:

For further details, please refer to Section 3.2.2.2.