Particulate Monitoring Systems

Installation & Operating Manual

Document No. 210-1003-M

Page 40

©2007

2:11

Thru

2:15

- 0

1

Bool

Not

Used

3

40609

Particulate process variable LO word

4 40610

0 5000

pA

Float

Particulate process variable HI word

5

40611

Averaged particulate process variable LO word

6 40612

0 5000

pA

Float

Averaged particulate process variable HI word

7

40737

Alarm level – Max alarm #1 LO word

8 40738

0 5000

pA

Float

Alarm level – Max alarm #1 HI word

9

40739

Alarm level – Pre-visible alarm #2 LO word

10 40740

0 5000

pA

Float

Alarm level – Pre-visible alarm #2 HI word

11

40769

0

600

Usint

Alarm delay – Max alarm #1

12

40770

0

600

Usint

Alarm delay – Pre-visible alarm #2

Output (O->T) Assembly Object (Class 0x04, Instance 0x66)

The following is a mapping of I/O values for the standard Ethernet/IP® assembly object instance
0x66. These are values that are sent from the Ethernet/IP® client (typically a PLC) to the
Ethernet/IP® server (control unit). The first word in the map contains the run/idle bit (bit 0). The
run/idle bit controls write access to the control unit. When the run/idle bit is set to 0 the control
unit is set to idle mode. In idle mode, the Ethernet/IP® server will allow read only access to the
control unit. When the run/idle bit is set to 1 the control unit is set to run mode. In run mode, the
Ethernet/IP® server will allow both read and write access to the control unit. The run/idle control
is defined for communications purposes only and has no affect on any other normal
control/sensing/alarming operation of the control unit. The output assembly size is 7 (16 bit
words).

Data Types

Bool – 1 bit Boolean discrete data

Usint – 16 bit unsigned integer analog data

Sint – 16 bit signed analog data

Float – 32 bit signed floating point analog data

Floating point values are represented in IEEE format (32-bit) where the 1

st

register is the LOW

word and the 2

nd

register is the HIGH word.

Output (O->T) Assembly Object (Class 0x04, Instance 0x66) Size 7 (16 bit words)

16-Bit

Word

Modbus

®

Range Range Units

Data

Type

Description

Address Address Min Max

0

-

0

1

Usint

Run/Idle mode setting (0=idle/read only, 1=run/read write)

1

40737

Alarm level – Max alarm #1 LO word

2 40738

0 5000 pA Float

Alarm level – Max alarm #1 HI word

3

40739

Alarm level – Pre-visible alarm #2 LO word

4 40740

0 5000 pA Float

Alarm level – Pre-visible alarm #2 HI word

5 40769 0 600 Sec Usint

Alarm

Delay

HI

Particulate

6

40770

0

600

Sec

Usint

Alarm Delay HI Delta P