6.4 Menu 3 Setup

Navigation within Menu 3 is similar to that described in Menu’s 1 and 2. Features designated with an
asterisk (*) are optional. Operation of optional features is dependant upon model and options selected
at the time of order. The following setup menus are based on firmware version 2.27 or higher.
















































Press the UP and DOWN keys at the same time from the main screen to enter the Menu 3 setup

screen. Use the UP/DOWN arrow keys to adjust a setting to the desired value. Press the ENTER

key to save the value and proceed to the next screen. Press the SETUP/ESCAPE key to return to

the main screen without saving the current parameter’s value.

Menu Item

Range

Definition

Signal

Filter

Frequency

0.033 – 2.0

Hz

This parameter controls the low-pass filtering of the input

signal. Setting the frequency lower gives a more stable

output reading. Setting the frequency higher gives a more
dynamic output reading. Signal filtering is applied to the

numeric readout only unless bar graph/4-20mA filtering is

ON (see setting below).

* Units of

Measure

1111 pA

2222 mg

This parameter sets the displayed and output units of

measure to be either pA or mg/m

3

. Conversion to mg/m

3

first requires correlation testing and instrument scaling.

Auto-

Range

Delay

1 – 30

Sec

This parameter controls how long the bar graph readout

must be at either extreme before it automatically switches

ranges. If the bar graph is switching ranges too often, the

auto-range delay should be increased.

* Peak Hold

Time

0 – 60

Sec

This parameter sets the amount of time a rapidly

occurring peak reading is displayed. Peak Hold is used

for processes that are very dynamic with spiking

readings.

* Bar Graph

&

4-20mA

Output

Filtering

Yes/No

This parameter enables or disables filtering of the bar

graph and the optional 4-20mA output. The filtering

applied is the Signal Filter Frequency parameter listed

above. Filtering is enabled by selecting YES and disabled

by selecting NO.

*

Correlation

Values

MINIMUM

and

MAXIMUM

(EM 70)

0 – 5000

pA1=0

pA2=5000

pA3=0

pA4=5000

These parameters are used to re-scale the output from

pA to mg/m

3

. Raw min/max values (pA1 and pA2) are

entered and equivalent Scaled min/max values (pA3 and

pA4) are entered. The control unit will convert the Raw

values to Scaled values automatically. To remove all

scaling, set Raw min=Scaled min and Raw max=Scaled

max. Example: 0-5000pA = 0-4000mg/m

3

pA1=0, pa2=5000, mg3=0, mg4=4000