OVERVIEW OF DEVCOM2000

Field devices such as flow, pressure, level, temperature transmitters, and valve positioners provide the physical
connection to the process. These devices allow the control system to monitor and manipulate process conditions.
HART devices maintain a real-time database of process, configuration, identification, and diagnostic information.
This information can be accessed using the HART Field Communications Protocol.

HART devices are capable of providing functions and features far beyond the basic task of providing a process
input or accepting a control output to manipulate process conditions. Many HART compatible device manufactures
create a DD (Device Description) describing all of these functions and features specific to that device. The DD also
provides information essential to the successful configuration and calibration of the device.

DevCom2000 uses these DD’s to access the data stored in a device, providing full configuration and setup support
for all registered HART DD’s.

DevCom2000 accesses and presents field device data based solely on its DD. No other files, information or custom
drivers are required. DevCom2000 is intended to monitor and configure a single device at a time, it is directly
connected to the current loop of the particular device and:

• Provides user interface to configure the HART field device,

• Provides a means to configure and view all the parameters related to HART field device, and

• Provides an option to view the detailed status and diagnostic capability of the device.

DevCom2000 allows viewing and modifying of field device parameters based on the DD. Using the device’s DD,
DevCom2000 performs various tests to verify the proper operation of the HART device. DevCom2000 runs as a
standalone software package and must have a HART compatible modem attached to the system to interrogate the
HART base devices.