Dwyer 1950G User Manual

Dwyer instruments, inc

background image

To order
specify Model
Number*
1950G-00-B-__
1950G-0-B-__
1950G-1-B-__
1950G-5-B-__
1950G-10-B-__
1950G-20-B-__

Operating
Range
Inches, W.C.
0.07 to 0.15
0.15 to 0.5
0.4 to 1.6
1.4 to 5.5
3.0 to 11.0
4.0 to 20.0

At Min.
Set Point
0.04
0.06
0.11
0.4
0.9
1.2

Approximate

Dead Band

At Max.
Set Point
0.06
0.11
0.29
0.9
1.8
3.0

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. Box 373 • Michigan City, IN 46360-0373, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

The Model 1950G Explosion-Proof Switch combines the best features
of the popular Series 1900 Pressure Switch with a compact explosion-
proof housing.

This unit is UL, CSA, FM listed for use in Class I, Groups A*, B, C, D,
Class II, Groups E, F, & G and Class III atmospheres and Directive
94/9/EC (ATEX) Compliant for II 2G Ex d IIB + H2 T6 Gb. IECEx

certified Ex d IIB + H2 T6 Gb (-40°C < Ta < + 60°C) units are available.

It is also totally rain-tight for outdoor installations. Six models allow set-
points from 0.07 to 20 inches W.C. ( 1.78 mm to 508.0 mm W.C.).

Easy access to the SPDT relay for electrical hook-up is provided by
removing the top plate of the aluminum housing. A captive screw allows
the cover to swing aside while remaining attached to the unit.
Adjustment to the set point of the switch can be made without
disassembly of the housing. The unit is very compact, about half the
weight and bulk of equivalent conventional explosion-proof switches.

Series 1950G – Integral Explosion-Proof Pressure Switches

Specifications - Installation and Operating Instructions

Bulletin E-57G

UL, CSA, FM Listed For

CL, I GR. A*, B, C, D - CL. II GR. E, F, G - CL. III

Directive 94/9/EC (ATEX) Compliant For

0344 II 2G Ex d IIB + H

2

T6 Gb

EC-Type Certificate Number: KEMA 03ATEX2402 X

ATEX Standards:

EN60079-0: 2009
EN60079-1: 2007

IECEx Certified for:

Ex d IIB + H

2

T6 Gb (-40°C < Ta < +60°C)

IECEx Certificate of Conformity:

IECEx DEK 11.0092X

IECEx Standards:

IEC 60079-0: 2007
IEC 60079-1: 2007

Model 1950G Switches:
Operating ranges and deadbands

Set Point

Adjustment

Screw

1/2˝ female
NPT
Electrical
Conduit
Connection

Vent Drain

Plug

Captive

Screw

*GR. A is Only.

External

Ground Screw

* Specify either 24 for 24 VDC, 120 for 120 VAC or 240 for 240 VAC

when ordering. Example: 1950G-00-B-120

* Add “NA” suffix for models with UL, CSA, and FM approvals only.

Example: 1950G-00-B-120-NA

Attention: Units with the “NA” suffix are not Directive 94/9/EC (ATEX)
compliant. These units are not intended for use in potentially explosive
atmospheres in the EU. These units may be CE marked for other
Directives of the EU.

SPECIFICATIONS
Service:
Air and compatible combustible gases.
Wetted Materials: Contact Factory.
Temperature Limits: 0 to 140°F (-17 to 60°C). Note: Set point drift may
occur with ambient temperature changes.
Pressure Limits: 45˝ w.c. (11.2 kPa) continuous; 10 psig (68.95 kPa)
surge.
Enclosure Rating: IP54, NEMA 3, 7 and 9.
Switch Type: 1 Form C relay (SPDT).
Electrical Rating: 10A, 120/240 VAC, 28 VDC. Resistive 50mA, 125
VDC.
Power Requirements: 24 VDC ±10%. 120 or 240 VAC ±10% optional.
Electrical Connections: Internal Terminal Block.
Process Connections: 1/8˝ female NPT.
Mounting Orientation: Diaphragm in vertical position. Consult factory for
other position orientations.
Set Point Adjustment: Screw type on top of housing.
Weight: 2 lb, 15.7 oz (1.35 kg).