beautypg.com

Easicool™ precision air conditioning, Te ch nic al x-t yp e v, Technical data upflow units x type – Airedale EasiCool 6kW 64kW User Manual

Page 93: Electrical data

background image

EasiCool™

Precision Air Conditioning

93

EasiCool Technical Manual 7525389 V1.1.0_02_2013

Te

ch

nic

al

X-T

yp

e

V

V50X2 - V60X2

V50X2-EZRE-0

V55X2-EZRE-0

V60X2-EZRE-0

Standard Condenser Match

1 x CR80

1 x CR80

1 x CR80

Max Mains Incoming Cable Size

mm²

50

50

50

Mains Supply

V

400V / 3PH + N / 50HZ

Control Circuit

VAC

24

24

24

Unit Data Full Function - X

(1)

Nominal Run Amps

A

87.8

91.6

96.6

Maximum Start Amps

A

235.0

210.9

246.4

Recommended Mains Fuse Size

A

100

125

125

Unit Data Cooling Only - X
Nominal Run Amps

(2)

A

50.7

54.5

59.5

Maximum Start Amps

A

191.7

167.6

203.1

Recommended Mains Fuse Size

A

63

63

80

Evaporator Fan - AC Motor Per Fan

Centrifugal Forward Curved Belt & Pulley AC - Designed to 25Pa ESP

Quantity

2

2

2

Maximum Electrical Input Power

(3)

kW

3.5

3.5

3.5

Full Load Amps

A

6.18

6.18

6.18

Locked Rotor Amps

A

43.3

43.3

43.3

Compressor - Per Compressor
Quantity x Motor Size

kW

2 x 8.4

2 x 9.47

2 x 10.85

Nominal Run Amps

A

15

16.9

19.4

Locked Rotor Amps

A

156

130

163

Type of Start

Direct On Line

Standard Condenser Match -

AC Motor - Per Fan
Quantity

3

3

3

Maximum Electrical Input Power

kW

0.6

0.6

0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

3

3

3

Number of Elements

12

12

12

Rating

kW

30

30

30

Current per Phase

A

43.30

43.30

43.30

Humidifier
Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.24

16.24

16.24

Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan

Centrifugal Forward Curved Belt & Pulley AC - Designed to 25Pa ESP

Quantity

2

2

2

Maximum Electrical Input Power

(3)

kW

4.6

4.6

4.6

Full Load Amps

A

8.12

8.12

8.12

Locked Rotor Amps

A

60.9

60.9

60.9

Standard Size Motor - EC Motor - Per Fan

Centrifugal Backward Curved DD EC - Designed to 25Pa ESP

Quantity

2

2

2

Quantity x Motor Size

(3)

kW

3.1

3.1

3.1

Full Load Amps

A

4.8

4.8

4.8

Condenser Fan Options
Standard Condenser Motor

- EC Motor - Per Fan
Quantity

3

3

3

Maximum Electrical Input Power

(3)

kW

0.73

0.73

0.73

Full Load Amps

A

3.3

3.3

3.3

Technical Data Upflow Units X Type

Electrical Data

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, these values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.