Technical Data Upflow Units X Type
Performance Data Standard Condenser
TC = Total Cooling
SC = Sensible Cooling
(1) All data quoted is gross
Cooling Capacity (1)
Ambient
Air On
25°C
30°C
35°C
40°C
(DB°C/%RH)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
V6X-EZRE CR12
22/50
6.2
6.1
6.2
6.1
6.2
6.1
5.9
5.9
24/45
6.5
6.5
6.5
6.5
6.4
6.4
6.1
6.1
26/40
6.8
6.8
6.8
6.8
6.7
6.7
6.4
6.4
V8X-EZRE CR16
22/50
7.9
7.9
7.9
7.9
7.9
7.9
7.5
7.5
24/45
8.2
8.2
8.2
8.2
8.2
8.2
7.8
7.8
26/40
8.6
8.6
8.6
8.6
8.6
8.6
8.3
8.3
V10X-EZRE CR16
22/50
10.3
10.3
10.3
10.3
10.2
10.2
9.7
9.7
24/45
10.8
10.8
10.8
10.8
10.6
10.6
10.1
10.1
26/40
11.2
11.2
11.2
11.2
11.0
11.0
10.6
10.6
V13X-EZRE CR22
22/50
13.4
12.4
13.4
12.4
13.2
12.3
12.5
11.9
24/45
13.9
13.7
13.9
13.7
13.7
13.6
13.0
13.0
26/40
14.4
14.4
14.4
14.4
14.2
14.2
13.5
13.5
V15X-EZRE CR22
22/50
15.2
14.5
15.2
14.5
14.8
14.3
14.1
13.8
24/45
15.8
15.7
15.8
15.7
15.4
15.4
14.7
14.7
26/40
16.2
16.2
16.2
16.2
15.9
15.9
14.9
14.9
V17X-EZRE CR30
22/50
17.5
16.6
17.5
16.6
17.3
16.4
16.3
15.8
24/45
18.1
18.1
18.1
18.1
17.8
17.8
16.8
16.8
26/40
18.6
18.6
18.6
18.6
18.3
18.3
17.3
17.3
V20X2-EZRE CR30
22/50
21.0
19.9
21.0
19.9
20.3
19.5
19.2
18.8
24/45
21.8
21.8
21.8
21.8
21.1
21.1
20.0
20.0
26/40
22.7
22.7
22.7
22.7
21.9
21.9
20.9
20.9
V22X2-EZRE CR50
22/50
21.6
21.3
21.6
21.3
21.6
21.3
20.7
20.7
24/45
22.5
22.5
22.5
22.5
22.5
22.5
21.6
21.6
26/40
23.5
23.5
23.5
23.5
23.5
23.5
22.6
22.6
V26X2-EZRE CR50
22/50
26.5
24.2
26.5
24.2
26.5
24.2
25.1
23.3
24/45
27.5
26.5
27.5
26.5
27.4
26.4
26.0
25.4
26/40
28.6
28.6
28.6
28.6
28.4
28.4
27.0
27.0
Operating Limits
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55%
Outdoor Temperature
-20°C to +41°C