V6X - V10X
Technical Data Upflow Units X Type
Electrical Data
V6X-EZRE-0
V8X-EZRE-0
V10X-EZRE-0
Standard Condenser Match
1 x CR12
1 x CR16
1 x CR16
Max Mains Incoming Cable Size
mm²
6
6
6
Mains Supply
V
400V / 3PH + N / 50HZ
Control Circuit
VAC
24
24
24
Unit Data Full Function - X
(1)
Nominal Run Amps
A
20.0
21.0
21.2
Maximum Start Amps
A
42.4
51.4
58.6
Recommended Mains Fuse Size
A
25
25
25
Unit Data Cooling Only - X
Nominal Run Amps
(2)
A
9.2
10.2
10.4
Maximum Start Amps
A
31.6
40.6
47.8
Recommended Mains Fuse Size
A
16
16
16
Evaporator Fan - EC Motor Per Fan
Centrifugal Forward Curved DD EC - Designed to 25Pa ESP
Quantity
1
1
1
Maximum Electrical Input Power
(3)
kW
1.3
1.3
1.15
Full Load Amps
A
5.6
5.6
4.8
Locked Rotor Amps
A
5.6
5.6
4.8
Compressor - Per Compressor
Quantity x Motor Size
kW
1 x 2
1 x 2.6
1 x 3.3
Nominal Run Amps
A
3.6
4.6
5.6
Locked Rotor Amps
A
26
35
43
Type of Start
Direct On Line
Standard Condenser Match - AC Motor - Per Fan
Quantity
1
1
1
Maximum Electrical Input Power
kW
0.27
0.27
0.27
Full Load Amps
A
1.1
1.1
1.1
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
1
1
1
Number of Elements
3
3
3
Rating
kW
7.5
7.5
7.5
Current per Phase
A
10.83
10.83
10.83
Humidifier
Capacity
kg/hr
3
3
3
Rating
kW
2.25
2.25
2.25
Full Load Amps
A
3.25
3.25
3.25
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Quantity
Maximum Electrical Input Power
(3)
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Standard Size Motor - EC Motor - Per Fan
Centrifugal Backward Curved DD EC - Designed to 25Pa ESP
Quantity
1
1
1
Quantity x Motor Size
(3)
kW
0.94
0.94
0.94
Full Load Amps
A
1.5
1.5
1.5
Condenser Fan Options
Standard Condenser Motor - EC Motor - Per Fan
Quantity
1
1
1
Maximum Electrical Input Power
(3)
kW
0.7
0.7
0.7
Full Load Amps
A
3.1
3.1
3.1
Mechanical
(1)
Entering air 24°C/45% RH ambient 35°C.
(2)
Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, these values may change with different ESP.
(3)
With Standard forward curved fan motors; Machine weight includes a refrigerant charge.
(4)
Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5)
For refrigerant charges, refer to
Unit Refrigerant Charge (kg/Circuit)
.
(6)
Based on air temperature of 15.5°C leaving the evaporator coil.
(7)
Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to
Low Pressure Hot Water
.
Electrical
(1)
Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard
forward curved fan motors, for optional data, please contact Airedale.
(2)
Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional
data, please contact Airedale.
(3)
Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.