Easicool™ precision air conditioning, Te ch nic al x-t yp e df, Technical data downflow units x type – Airedale EasiCool 6kW 64kW User Manual

Page 63: Electrical data, Df6x - df10x

background image

EasiCool™

Precision Air Conditioning

63

EasiCool Technical Manual 7525389 V1.1.0_02_2013

Te

ch

nic

al

X-T

yp

e

DF

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, these values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Technical Data Downflow Units X Type

Electrical Data

DF6X-EZRE-0

DF8X-EZRE-0

DF10X-EZRE-0

Standard Condenser Match

1 x CR12

1 x CR16

1 x CR16

Max Mains Incoming Cable Size

mm²

6

6

6

Mains Supply

V

400V / 3PH + N / 50HZ

Control Circuit

VAC

24

24

24

Unit Data Full Function - X

(1)

Nominal Run Amps

A

20.0

21.0

21.2

Maximum Start Amps

A

42.4

51.4

58.6

Recommended Mains Fuse Size

A

25

25

25

Unit Data Cooling Only - X
Nominal Run Amps

(2)

A

9.2

10.2

10.4

Maximum Start Amps

A

31.6

40.6

47.8

Recommended Mains Fuse Size

A

16

16

16

Evaporator Fan - EC Motor Per Fan

Centrifugal Forward Curved DD EC - Designed to 25Pa ESP

Quantity

1

1

1

Maximum Electrical Input Power

(3)

kW

1.3

1.3

1.15

Full Load Amps

A

5.6

5.6

4.8

Locked Rotor Amps

A

5.6

5.6

4.8

Compressor - Per Compressor
Quantity x Motor Size

kW

1 x 2

1 x 2.6

1 x 3.3

Nominal Run Amps

A

3.6

4.6

5.6

Locked Rotor Amps

A

26

35

43

Type of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Quantity

1

1

1

Maximum Electrical Input Power

kW

0.27

0.27

0.27

Full Load Amps

A

1.1

1.1

1.1

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

1

1

1

Number of Elements

3

3

3

Rating

kW

7.5

7.5

7.5

Current per Phase

A

10.83

10.83

10.83

Humidifier
Capacity

kg/hr

3

3

3

Rating

kW

2.25

2.25

2.25

Full Load Amps

A

3.25

3.25

3.25

Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Quantity
Maximum Electrical Input Power

(3)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Size Motor - EC Motor - Per Fan

Centrifugal Backward Curved DD EC - Designed to 25Pa ESP

Quantity

1

1

1

Maximum Electrical Input Power

(3)

kW

0.94

0.94

0.94

Full Load Amps

A

1.5

1.5

1.5

Condenser Fan Options
Standard Condenser Motor - EC Motor - Per Fan
Quantity

1

1

1

Maximum Electrical Input Power

(3)

kW

0.7

0.7

0.7

Full Load Amps

A

3.1

3.1

3.1

DF6X - DF10X