Easicool™ precision air conditioning, Ins ta lla tio n, Refrigerant charging guide – Airedale EasiCool 6kW 64kW User Manual
Page 44: Unit refrigerant charge

EasiCool™
Precision Air Conditioning
44
EasiCool Technical Manual 7525389 V1.1.0_02_2013
Ins
ta
lla
tio
n
Indoor Unit
Standard Condenser
Larger Condenser
(IR)
kg/Circuit
HGRH
(OR)
kg/Circuit
(OR)
kg/Circuit
kg/Circuit
V6X-EZRE
1
1.1
CR12
1.4
CR16
2.7
V8X-EZRE
1
1.1
CR16
2.7
CR22
2.2
V10X-EZRE
1
1.1
CR16
2.7
CR22
2.2
V13X-EZRE
1.5
1.7
CR22
2.2
CR30
4.3
V15X-EZRE
1.5
1.7
CR22
2.2
CR30
4.3
V17X-EZRE
1.5
1.7
CR30
4.3
CR50
4.9
V20X2-EZRE
2.2
2.5
CR30
4.3
CR50
4.9
V22X2-EZRE
2.2
2.5
CR50
4.9
CR65
9.8
V26X2-EZRE
2.2
2.5
CR50
4.9
CR65
9.8
V28X-EZRE
2.7
3
CR50
4.9
CR65
9.8
V28X2-EZRE
2.6
2.9
CR50
4.9
CR65
9.8
V31X-EZRE
2.7
3
CR50
4.9
CR65
9.8
V31X2-EZRE
2.6
2.9
CR50
4.9
CR65
9.8
V35X-EZRE
3.3
3.7
CR50
4.9
CR65
9.8
V35X2-EZRE
3.3
3.7
CR50
4.9
CR65
9.8
V40X-EZRE
3.5
4
CR65
9.8
CR80
8.4
V40X2-EZRE
3.6
4.1
CR65
9.8
CR80
8.4
V45X2-EZRE
4.2
4.7
CR80
8.4
CR105
16.7
V50X2-EZRE
4.5
5.1
CR80
8.4
CR105
16.7
V55X2-EZRE
5.2
5.8
CR80
8.4
CR105
16.7
V60X2-EZRE
5.4
5.9
CR80
8.4
CR105
16.7
Indoor Unit
Standard Condenser
Larger Condenser
(IR)
kg/Circuit
HGRH
(OR)
kg/Circuit
(OR)
kg/Circuit
kg/Circuit
DF6X-EZRE
1
1.1
CR12
1.4
CR16
2.7
DF8X-EZRE
1
1.1
CR16
2.7
CR22
2.2
DF10X-EZRE
1
1.1
CR16
2.7
CR22
2.2
DF13X-EZRE
1.5
1.7
CR22
2.2
CR30
4.3
DF15X-EZRE
1.5
1.7
CR22
2.2
CR30
4.3
DF17X-EZRE
1.5
1.7
CR30
4.3
CR50
4.9
DF20X2-EZRE
2.2
2.4
CR30
4.3
CR50
4.9
DF22X2-EZRE
2.2
2.4
CR50
4.9
CR65
9.8
DF26X2-EZRE
2.2
2.4
CR50
4.9
CR65
9.8
DF28X-EZRE
2.7
3
CR50
4.9
CR65
9.8
DF31X-EZRE
2.7
3
CR50
4.9
CR65
9.8
DF35X-EZRE
3.3
3.7
CR50
4.9
CR65
9.8
DF40X-EZRE
3.5
3.9
CR65
9.8
CR80
8.4
DF45X-EZRE
4.2
4.6
CR80
8.4
CR105
16.7
DF50X2-EZRE
4.5
5
CR80
8.4
CR105
16.7
DF55X2-EZRE
5.3
5.8
CR80
8.4
CR105
16.7
DF60X2-EZRE
5.4
5.9
CR80
8.4
CR105
16.7
Refrigerant Charging Guide
The following information can be used to estimate the refrigerant quantity required in a typical split system installation.
Unit Refrigerant Charge
(kg / Circuit)
The following information can be used to estimate the refrigerant quantity required in a typical split system installation.
The table shows the refrigerant charge / circuit for the indoor and outdoor units.