Easicool™ precision air conditioning, Te ch nic al x-t yp e df, Technical data downflow units x type – Airedale EasiCool 6kW 64kW User Manual
Page 57: Performance data standard condenser, Operating limits

EasiCool™
Precision Air Conditioning
57
EasiCool Technical Manual 7525389 V1.1.0_02_2013
Te
ch
nic
al
X-T
yp
e
DF
Cooling Capacity (1)
Ambient
Air On
25°C
30°C
35°C
40°C
(DB°C/%RH)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
DF28X-EZRE CR50
22/50
25.0
24.3
25.0
24.3
25.0
24.3
23.8
23.4
24/45
26.1
26.1
26.1
26.1
26.1
26.1
24.9
24.9
26/40
27.4
27.4
27.4
27.4
27.3
27.3
26.2
26.2
DF31X-EZRE CR50
22/50
28.4
28.2
28.4
28.2
28.2
28.1
26.8
26.8
24/45
29.7
29.7
29.7
29.7
29.4
29.4
28.0
28.0
26/40
31.2
31.2
31.2
31.2
30.8
30.8
29.5
29.0
DF35X-EZRE CR50
22/50
32.9
32.5
32.9
32.5
32.3
31.9
30.7
30.5
24/45
34.5
34.5
34.5
34.5
33.7
33.7
32.2
32.2
26/40
36.3
36.3
36.3
36.3
35.5
34.9
34.2
32.5
DF40X-EZRE CR65
22/50
36.7
36.6
36.7
36.6
36.6
36.5
34.7
34.7
24/45
38.5
38.5
38.5
38.5
38.2
38.2
36.4
36.4
26/40
40.4
40.4
40.4
40.4
40.1
40.0
38.6
37.4
DF45X-EZRE CR80
22/50
41.4
39.2
41.4
39.2
41.4
39.2
39.5
37.9
24/45
43.2
42.9
43.2
42.9
43.2
42.9
41.1
41.1
26/40
45.1
45.1
45.1
45.1
45.0
45.0
43.0
43.0
DF50X2-EZRE CR80
22/50
48.2
45.1
48.2
45.1
47.8
44.8
45.3
43.1
24/45
50.2
49.3
50.2
49.3
49.6
48.8
47.1
46.9
26/40
52.3
52.3
52.3
52.3
51.5
51.5
49.0
49.0
DF55X2-EZRE CR80
22/50
54.5
48.8
54.5
48.8
53.4
48.1
50.5
46.3
24/45
56.6
53.7
56.6
53.7
55.3
52.8
52.4
50.9
26/40
58.7
58.7
58.7
58.7
57.2
57.2
54.3
54.3
DF60X2-EZRE CR80
22/50
61.5
54.3
61.5
54.3
59.4
53.0
56.2
51.1
24/45
63.8
59.6
63.8
59.6
61.5
58.1
58.2
55.9
26/40
66.1
65.2
66.1
65.2
63.5
63.3
60.2
60.2
Technical Data Downflow Units X Type
Performance Data
Standard Condenser
TC = Total Cooling
SC = Sensible Cooling
(1) All data quoted is gross
Operating Limits
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55% (based upon 24°C Dry Bulb)
Outdoor Temperature
-20°C to +41°C