EasiCool™
Precision Air Conditioning
W x D x H
A
B
C
D
E
F
G
DF6
X/WX
mm
670 x 670 x 1940
640
270
216
238
N/A
50
268
DF8
X/WX
mm
670 x 670 x 1940
640
270
183
304
N/A
50
268
DF10
X/WX
mm
670 x 670 x 1940
640
270
167
337
N/A
50
295
DF13
X/WX
mm
990 x 670 x 1940
960
590
326
337
N/A
50
295
DF15
X/WX
mm
990 x 670 x 1940
960
590
294
401
N/A
50
347
DF17
X/WX
mm
990 x 670 x 1940
960
590
294
401
N/A
50
347
DF20
X2/WX2
mm
1310 x 670 x 1940
1280
455
166
337
303
50
295
DF22
X2/WX2
mm
1310 x 670 x 1940
1280
455
166
337
303
50
295
DF26
X2/WX2
mm
1310x 670 x 1940
1280
455
166
337
303
50
295
(1)
Standard forward airflow direction.
(2)
Optional reverse airflow direction.
(3)
Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale.
(4)
Base mains cable entry.
(5)
Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
(6)
Shaded area denotes fan discharge aperture. Optional EC fan motor discharge aperture provided with protective mesh, not shown.
(7)
M6 fixing hole positions.
(8)
Units fitted with optional EC fan motors require a floorstand.
1
2
6 - 10
13 - 17
20 - 26
3
67
0
A
64
0
27
0
15
20
0
B
15
200
D
C
F
G
A
B
D
C
A
5
B
B
D
C
D
E
4
6
7
19
40
670
990
1310
Dimensional & Installation Data
Dimensions
DF6 - DF26 - Standard Airflow Configuration (mm) with Standard EC Fan Motors
32
EasiCool Technical Manual 7525389 V1.1.0_02_2013