Easicool™ precision air conditioning – Airedale EasiCool 6kW 64kW User Manual
Page 19

EasiCool™
Precision Air Conditioning
System Configuration
Features
Downflow
Upflow
X Type
WX Type
X Type
WX Type
Heating
Electric Heat
○
○
○
○
Hot gas Reheat
○
–
○
–
Low Pressure Hot Water
○
○
○
○
Humidification
Humidifier
○
○
○
○
Hot Water Condensate Pump
○
○
○
○
Low Conductivity (Soft Water) Bottle
○
○
○
○
Standard Conductivity (Moderate/Hard Water) Bottle
○
○
○
○
High Conductivity (Very Hard Water) Bottle
○
○
○
○
Cleanable Humidifier Bottle
○
○
○
○
●
Standard Feature
○
Optional Feature
–
Not Available
Heating and Humidification
Heating
Hot Gas Re-Heat (HGRH)
(X Models)
Refer to Hot Gas Re-Heat (HGRH).
Or
Electric Heating
Multi-stage finned electric heating elements complete with auto and manual reset overheat cut-out protection.
Electric Heating Thyristor Control
Offers precision control between 0 - 100% via the microprocessor.
Or
Low Pressure Hot Water
A low pressure hot water coil constructed of refrigeration quality copper tube and mechanically bonded aluminium fins
can be factory fitted.
Frost protection is fitted to prevent freezing of the low pressure hot water coil assembly.
Proportional heating control is provided by a factory fitted 3 port, raise/lower type, modulating valve.
Access to the Right hand side of the unit is required to set up the regulating valve
19
EasiCool Technical Manual 7525389 V1.1.0_02_2013