Easicool™ precision air conditioning, Te ch nic al x-t yp e df, Technical data downflow units x type – Airedale EasiCool 6kW 64kW User Manual
Page 59: Performance data larger condenser, Operating limits

EasiCool™
Precision Air Conditioning
59
EasiCool Technical Manual 7525389 V1.1.0_02_2013
Te
ch
nic
al
X-T
yp
e
DF
Cooling Capacity (1)
Ambient
Air On
25°C
30°C
35°C
40°C
45°C
(DB°C/%RH) TC (kW) SC (kW)
TC (kW) SC (kW)
TC (kW) SC (kW)
TC (kW) SC (kW)
TC (kW) SC (kW)
DF28X-EZRE CR65
22/50
25.0
24.3
25.0
24.3
25.0
24.3
24.2
23.8
23.1
22.9
24/45
26.1
26.1
26.1
26.1
26.1
26.1
25.3
25.3
24.3
24.3
26/40
27.4
27.4
27.4
27.4
27.4
27.4
26.6
26.6
25.7
25.4
DF31X-EZRE CR65
22/50
28.4
28.2
28.4
28.2
28.4
28.2
27.3
27.3
26.1
26.1
24/45
29.7
29.7
29.7
29.7
29.7
29.7
28.6
28.6
27.4
27.4
26/40
31.2
31.2
31.2
31.2
31.2
31.2
30.1
29.9
29.0
28.0
DF35X-EZRE CR65
22/50
32.9
32.5
32.9
32.5
32.9
32.5
31.4
31.2
29.9
29.9
24/45
34.5
34.5
34.5
34.5
34.5
34.5
32.9
32.9
31.5
31.5
26/40
36.3
36.3
36.3
36.3
36.2
36.2
34.8
33.8
33.8
31.4
DF40X-EZRE CR80
22/50
36.7
36.6
36.7
36.6
36.7
36.6
35.3
35.3
33.7
33.7
24/45
38.5
38.5
38.5
38.5
38.5
38.5
37.0
37.0
35.5
35.5
26/40
40.4
40.4
40.4
40.4
40.4
40.4
39.1
38.3
37.9
35.8
DF45X-EZRE CR105
22/50
41.4
39.2
41.4
39.2
41.4
39.2
40.0
38.2
38.2
36.9
24/45
43.2
42.9
43.2
42.9
43.2
42.9
41.7
41.7
39.9
39.9
26/40
45.1
45.1
45.1
45.1
45.1
45.1
43.6
43.6
41.8
41.8
DF50X2-EZRE CR105
22/50
48.2
45.1
48.2
45.1
48.2
45.1
46.1
43.6
43.8
42.0
24/45
50.2
49.3
50.2
49.3
50.2
49.3
48.0
47.5
45.6
45.6
26/40
52.3
52.3
52.3
52.3
52.3
52.3
49.9
49.9
47.5
47.5
DF55X2-EZRE CR105
22/50
54.5
48.8
54.5
48.8
54.4
48.7
51.6
47.0
48.9
45.3
24/45
56.6
53.7
56.6
53.7
56.4
53.5
53.5
51.6
50.7
49.7
26/40
58.7
58.7
58.7
58.7
58.3
58.3
55.4
55.4
52.6
52.6
DF60X2-EZRE CR105
22/50
61.5
54.3
61.5
54.3
60.8
53.8
57.6
51.9
54.3
49.9
24/45
63.8
59.6
63.8
59.6
62.9
59.0
59.6
56.9
56.3
54.7
26/40
66.1
65.2
66.1
65.2
64.9
64.4
61.7
61.7
58.4
58.4
Technical Data Downflow Units X Type
Performance Data
Larger Condenser
TC = Total Cooling
SC = Sensible Cooling
(1) All data quoted is gross
Operating Limits
Indoor Air Temperature
+18°C to +28°C
Indoor RH%
+40% to +55% (based upon 24°C Dry Bulb)
Outdoor Temperature
-20°C to +41°C