To enter the Enable mode, press the UP and DOWN keys while in CtrL or oFF modes. All the
display lamps will light. After 2 seconds, the display will show Cchg and the pen(s) will move
to and remain at a point above the top graduation on the chart. Continue to press the UP and
DOWN keys, after 2 additional seconds, the display will show P dn and the Pen(s) are driven
below the bottom graduation on the chart. After 6 more seconds, the display will show EnAb.
Release the keys and the display will change to EtSt. Press and release the DOWN key and
each mode to be enabled/disabled will be displayed. With the enable mode prompt for the
desired mode displayed press the SCROLL key to verify that the displayed mode is either on
(enabled) or oFF (disabled). Press the DOWN key to turn off the mode, press the UP key to
turn on the mode or press the SCROLL key to advance the display to the next enable mode
prompt. Use the "Your Setting" column in the table to record your settings.
A hardware jumper located on the Processor Board (See Appendix A-1, Page 67) can be
used to lock/unlock the Enable mode. When the jumper is moved to the locked position, entry
into the Enable mode is not possible until the jumper is moved to the unlocked position.
1 Test Mode
EtSt on or oFF oFF
2 Calibration Mode
ECAL
on or oFF oFF
3
Program Mode
EPro
on or oFF on
4
Tune Mode
Etun
on or oFF on
5
Manual (Stby) Mode
ESby
on or oFF on
6
Profile Continue mode
EPC
on or oFF oFF
7
Profile Entry Mode
EPE
on or oFF
on
7
Setpoint Change
ESPC
on or oFF on