West Control Solutions MRC 7000 Profiler Manual User Manual
Page 30

30
1
Input Select
inPS
0=J T/C degrees C
1
1=J T/C degrees F
2=K T/C degrees C
3=K T/C degrees F
4=T T/C degrees C
5=T T/C degrees F
6=R T/C degrees C
7=R T/C degrees F
8=S T/C degrees C
9=S T/C degrees F
10=E T/ C degrees C
11=E T/C degrees F
12=B T/ C degrees C
13=B T/C degrees F
14=N T/ C degrees C
15=N T/C degrees F
16=C T/ C degrees C
17=C T/C degrees F
20=RTD degrees C
21=RTD degrees F
30=0 to 5 VDC
31=1 to 5 VDC
32=0 to 50 mVDC
33=10 to 50 mVDC
34=0 to 25 mVDC
2
Input Correction
iCor
-300 to 300 degrees/units
0
3
Output 1
out1
0 = None
0
1=On-Off- Direct
2=On-Off- Reverse
3=Time Proportioning- Direct
4=Time Proportioning -Reverse
5=Current Proportioning -Direct
6=Current Proportioning -Reverse
7=Position Proportioning (open)
4
Output 1 Percent
o1uL
0 to 100 percent
100
Upper Limit
(o1uLand o1LL will
not be seen if out1 = 0,1,2)
5
Output 1 Percent
o1LL
0 to 100 percent
0
Lower Limit
6
Output 2
out2
0 = None (Position
0
Proportioning - Direct Closed)
1=On-Off- Direct
2=On-Off- Reverse
3=Time Proportioning- Direct
4=Time Proportioning-Reverse
5=Current Proportioning- Direct
6=Current Proportioning -Reverse
7=Position Proportioning
(Reverse/Closed)
7
Output 2 Percent
o2uL
0 to 100 percent
100
Upper Limit (o2uL and
o2LL will not been seen if
out2 = 0,1,2,7)
8
Output 2 Percent
o2LL
0 to 100 percent
0
Lower Limit
NOTE:
Fault Detection is not functional
for 0-5V or 0-20mA inputs.
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODES SETTINGS
SETTING SETTING