West Control Solutions MRC 7000 Profiler Manual User Manual

Page 32

background image

32

24

Display Filter Factor

dFF

1 to 20

1

1= no filtering
(number of values averaged)

25

Process Filter Factor

PFF

Same selection as dFF

1

26

Process Value Output

Pout

0=Not selected

0

Retransmission

1=Selected

(If Pout =0 then Pou and
PoL will not be displayed)

27

Process Output

Pou

-9999 to 9999

2000

Upper Value

28

Process Output

PoL

-9999 to 9999

0

Lower Value

29

Chart Range

Cru

-9999 to 9999

200

Upper Value

30

Chart Range

CrL

-9999 to 9999

0

Lower Value

31

Proportional

P1EC

0 to 100%

0

Output 1 Action
on Error Condition
(If out1= 0,1,2 then
P1EC will not be displayed)

32

Proportional

P2EC

0 to 100%

0

Output 2 Action
on Error Condition
(If out2 = 0,1,2,7 then
P2EC will not be displayed)

33

Pen Action on

PAEC

0 or 1

1

Error Condition

0 = Pen goes to 0 % of chart
1 = Pen goes to 100 % of chart

Pressing the SCROLL key with the PAEC parameter value displayed in the Pen 1 window will
advance the display of a single pen instrument to the unit parameters. Pressing the SCROLL
key with the PAEC parameter displayed in the Pen 1 window of a two pen instrument will
advance the display to be PEns in the Pen 2 window. The Pen 2 Program mode parameter
selections can be made now. Pressing the SCROLL key with the PAEC parameter value
displayed in the Pen 2 window will cause the display to advance to the unit parameters
displayed in the Pen 1 window.

UNIT PARAMETERS

34

Relay A Assignment

rLyA

0 to 14

0

1=Assigned to Alarm 1-Pen 1
2=Assigned to Alarm 2-Pen 1
3=Assigned to Alarm 1-Pen 2
4=Assigned to Alarm 2-Pen 2
5=Assigned to Output 1-Pen 1
6=Assigned to Output 2-Pen 1
7=Assigned to Output 1-Pen 2
8=Assigned to Output 2-Pen 2
9=Assigned to Event 1
10=Assigned to Event 2
11=Assigned to Event 3
12=Assigned to Event 4
13=Assigned to Event 5
14=Assigned to Event 6

DISPLAY AVAILABLE

FACTORY YOUR

STEP

DESCRIPTION

CODES SETTINGS

SETTING SETTING