West Control Solutions MRC 7000 Profiler Manual User Manual
Page 32

32
24
Display Filter Factor
dFF
1 to 20
1
1= no filtering
(number of values averaged)
25
Process Filter Factor
PFF
Same selection as dFF
1
26
Process Value Output
Pout
0=Not selected
0
Retransmission
1=Selected
(If Pout =0 then Pou and
PoL will not be displayed)
27
Process Output
Pou
-9999 to 9999
2000
Upper Value
28
Process Output
PoL
-9999 to 9999
0
Lower Value
29
Chart Range
Cru
-9999 to 9999
200
Upper Value
30
Chart Range
CrL
-9999 to 9999
0
Lower Value
31
Proportional
P1EC
0 to 100%
0
Output 1 Action
on Error Condition
(If out1= 0,1,2 then
P1EC will not be displayed)
32
Proportional
P2EC
0 to 100%
0
Output 2 Action
on Error Condition
(If out2 = 0,1,2,7 then
P2EC will not be displayed)
33
Pen Action on
PAEC
0 or 1
1
Error Condition
0 = Pen goes to 0 % of chart
1 = Pen goes to 100 % of chart
Pressing the SCROLL key with the PAEC parameter value displayed in the Pen 1 window will
advance the display of a single pen instrument to the unit parameters. Pressing the SCROLL
key with the PAEC parameter displayed in the Pen 1 window of a two pen instrument will
advance the display to be PEns in the Pen 2 window. The Pen 2 Program mode parameter
selections can be made now. Pressing the SCROLL key with the PAEC parameter value
displayed in the Pen 2 window will cause the display to advance to the unit parameters
displayed in the Pen 1 window.
UNIT PARAMETERS
34
Relay A Assignment
rLyA
0 to 14
0
1=Assigned to Alarm 1-Pen 1
2=Assigned to Alarm 2-Pen 1
3=Assigned to Alarm 1-Pen 2
4=Assigned to Alarm 2-Pen 2
5=Assigned to Output 1-Pen 1
6=Assigned to Output 2-Pen 1
7=Assigned to Output 1-Pen 2
8=Assigned to Output 2-Pen 2
9=Assigned to Event 1
10=Assigned to Event 2
11=Assigned to Event 3
12=Assigned to Event 4
13=Assigned to Event 5
14=Assigned to Event 6
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODES SETTINGS
SETTING SETTING