Table 3-2 tune mode configuration procedure – West Control Solutions MRC 7000 Profiler Manual User Manual

Page 36

background image

36

DISPLAY AVAILABLE

FACTORY YOUR

STEP

DESCRIPTION

CODES SETTINGS

SETTING SETTING

TABLE 3-2 TUNE MODE CONFIGURATION PROCEDURE

The Tune mode allows the entry, review or altering of the process control Tune adjustments
and alarm setting(s).

To enter the Tune mode, press and release the SCROLL key until tunE is displayed, then
press the DOWN key. Press the SCROLL key to advance the display through the parameters
and their values. Use the UP and DOWN keys to select (adjust) the values. Each time the
DOWN key is pressed while a parameter code is being displayed, such as SoP, the next
parameter code in the sequence will be displayed (PAL1).

After selecting a parameter, press the SCROLL key to proceed to the next parameter. Pen 1
selections will appear in the Pen 1 window and the Pen 2 ( if provided) selections will appear
in the Pen 2 window after the Pen 1 parameters have been displayed. After all selections
have been made, press the UP key with a parameter in the display (not a setting) to exit the
mode.

For illustration purposes, all available Tune mode parameters have been listed. The
parameters that will appear on the specfic instrument will depend upon the parameter
selections previously made in the Program mode.

For future reference, record the parameter selections for the application in the "Your Setting"
column and on the Software Reference Sheet in Appendix E (page 78).

To prevent unauthorized changes to the Tune mode, the mode can be disabled (turned off) in
the Enable mode.

The Tune mode is adjusted on-line. The instrument will react to changes as they are
made.

1

Second Output Position

SoP

-1000 to 1000 units

0

(Will not be seen if out2=0,7)

2

Process Alarm 1

PAL1

-9999 to 9999 units

0

(The Alarm setting seen
will depend upon the Alarm
selected in the Program mode)

3

Deviation Alarm 1

dAL1

-3000 to 3000 units

0

4

Deviation Band Alarm 1

bAL1

1 to 3000 units

1

5

Process Alarm 2

PAL2

-9999 to 9999 units

0

6

Deviation Alarm 2

dAL2

-3000 to 3000 units

0

7

Deviation Band Alarm 2

bAL2

1 to 3000 units

1

8

Proportional Band

Pb1

1 to 3000 units

100

Output 1 (Will only be seen
if out1=3,4,5,6,7)

9

Proportional Band

Pb2

1 to 3000 units

100

Output 2 (Will only be
seen if out2=3,4,5,6)

10

Manual Reset

rSEt

-1500 to 1500 units

0

(Will only be seen if
Pb1/Pb2 were shown)

11

Automatic Reset

ArSt

0.0 to 100.0 repeats

0.0

Integration

per minute

(Will be seen if Pb1 or
Pb2 was shown)