West Control Solutions MRC 7000 Profiler Manual User Manual
Page 31

31
9
Alarm 1
AL1
0 to 6
0
the Alarm Point
0 = None
is selected in the
1=Process Alarm-Direct
Tune mode
2=Process Alarm-Reverse
3=Deviation Alarm-Direct
4=Deviation Alarm-Reverse
5=Deviation Band Alarm-Open within band
6=Deviation Band Alarm-Closed within band
10
Alarm 2
AL2
Same selections as Alarm 1
0
11
Display Select
diSP
1=Process value only
1
2=Process value/setpoint
3=Deviation only
4=Deviation and setpoint
5=Setpoint only
12
Decimal Position
dPoS
0 to 3
0
0=None
1=One decimal place
2=Two decimal places
3=Three decimal places
RTD and thermocouple inputs
are limited to either 0 or 1 decimal positions
13
Engineering Units
Euu
-9999 to 9999
1000
Upper Value (Euu and
EuL will be seen if the pen
input select = 30,31,32,33,34)
14
Engineering Units
EuL
-9999 to 9999
0
Lower Value
15
Hysteresis for
HyCo
0 to 300
3
Control Outputs
Width of Hysteresis Band
(See page 70 for definition)
16
Hysteresis for
HyAo
0 to 300
3
Alarm Outputs
Width of Hysteresis Band
(see page 70 for definition)
17
Remote Setpoint (Pen 2 only) rSP
0 to 2
0
If rSP is set to zero
0=Not Used
then rSPu and rSPL
1=1 to 5 VDC
are not seen
2=0 to 5 VDC
18
Remote Setpoint
rSPu
-9999 to 9999
1400
Upper Value (Pen 2 only)
19
Remote Setpoint
rSPL
-9999 to 9999
0
Lower Value (Pen 2 only)
20
Setpoint Upper Limit
SPuL
-9999 to 9999
1400
21
Setpoint Lower Limit
SPLL
-9999 to 9999
0
22
Automatic Transfer
AtFr
0 to 2
0
0 = No Automatic Transfer
1=Transfers when the process
value goes below the setpoint
2=Transfers when the process
value goes above the setpoint
23
Process Rounding
Prnd
0 to 100
0
of Displayed Value
0 = No rounding
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODES SETTINGS
SETTING SETTING