11 technical data 51, Technical data 51, Current signal measuring range 51 – West Control Solutions KS 42-1 User Manual
Page 51: Resistance thermometer measuring range 51, Thermocouple measuring range 51, Voltage signal measuring range 51, 11 technical data, Technical data

11
Technical data
INPUTS
PROCESS VALUE INPUT INP1
Resolution:
> 14 bits
Decimal point:
0 to 3 digits behind the decimal point
Dig. input filter:
adjustable 0,000...9999 s
Scanning cycle:
100 ms
Measured value
correction:
2-point or offset correction
Thermocouples
r
Table 1 (page 53 )
Input resistance:
³1 MW
Effect of source resistance:
1
mV/W
Cold-junction compensation
Maximal additional error:
± 0,5 K
Sensor break monitoring
Sensor current:
£ 1 mA
Configurable output action
Resistance thermometer
r
Table 2 (page 53 )
Connection:
2 or 3-wire
Lead resistance:
max. 30 Ohm
Input circuit monitor:
break and short circuit
Special measuring range
BlueControl (engineering tool) can be used to
match the input to sensor KTY 11-6
(characteristic is stored in the controller).
Physical measuring range:
0...4500 Ohm
Linearization segments
16
Current and voltage signals
r
Table 3 (page 53 )
Span start, end of
span:
anywhere within measuring
range
Scaling:
selectable -1999...9999
Linearization:
16 segments, adaptable with
BlueControl
Decimal point:
adjustable
Input circuit monitor: 12,5% below span start (2mA, 1V)
SUPPLEMENTARY INPUT INP2
Resolution:
> 14 bits
Scanning cycle:
100 ms
Accuracy:
< 0,5 %
Heating current measurement
via current transformer (
® Accessory equipment)
Measuring range: 0...50mA AC
Scaling:
adjustable -1999...0,000...9999 A
Current measuring range
Technical data as for INP1
CONTROL INPUT DI1
Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.
Switched voltage:
2,5 V
Current:
50
mA
CONTROL INPUTS DI2, DI3 (OPTION)
Configurable as switch or push-button!
Optocoupler input for active triggering
Nominal voltage
24 V DC external
Current sink (IEC 1131 type 1)
Logic “0”
-3...5 V
Logic “1”
15...30 V
Current requirement
approx.. 5 mA
TRANSMITTER SUPPLY U
T
(OPTION)
Power:
22 mA /
³18 V
If the universal output OUT3 is used there may
be no external galvanic connection between
measuring and output circuits!
GALVANIC ISOLATION
Safety isolation
Function isolation
OUTPUTS
RELAY OUTPUTS OUT1, OUT2
Contact type:
2 NO contacts with common
connection
Max. contact rating: 500 VA, 250 V, 2A at 48...62Hz,
resistive load
Min. contact rating: 6V, 1 mA DC
Technical data
Operating KS4x-1
51
Power supply
connections
Process value input INP1
Supplementary input INP2
Digital input di1
Relay outputs OUT 1,2
RS422/485 interface
Relay output OUT3
Digital inputs di2, 3
Universal output OUT3
Transmitter supply U
T