Configuration level
Operating KS4x-1
27
Configuration
Name
Value range Description
Default
SP.E
Switching to external setpoint SP.E
0
0
no function (switch-over via interface is possible)
1
active
2
DI1
3
DI2 (only visible with OPTION)
4
DI3 (only visible with OPTION)
Y2
Y/Y2 switching
0
0
no function (switch-over via interface is possible)
2
DI1
3
DI2 (only visible with OPTION)
4
DI3 (only visible with OPTION)
6
Ò key
mAn
Automatic/manual switching
0
0
no function (switch-over via interface is possible)
1
always activated (manual station)
2
DI1
3
DI2 (only visible with OPTION)
4
DI3 (only visible with OPTION)
6
Ò key
C.oFF
Switching off the controller
0
0
no function (switch-over via interface is possible)
2
DI1
3
DI2 (only visible with OPTION)
4
DI3 (only visible with OPTION)
6
Ò key
m.Loc
Blockage of hand function
0
0
no function (switch-over via interface is possible)
2
DI1
3
DI2 (only visible with OPTION)
4
DI3 (only visible with OPTION)
Err.r
Reset of all error list entries
0
0
no function (switch-over via interface is possible)
2
DI1
3
DI2 (only visible with OPTION)
4
DI3 (only visible with OPTION)
6
Ò key
P.run
Programmer Run/Stop (see page 44)
0
0
no function (switch-over via interface is possible)
2
DI1
3
DI2 (only visible with OPTION)
4
DI3 (only visible with OPTION)
di.Fn
Function of digital inputs (valid for all inputs)
0
0
direct
1
inverse
2
toggle key function
fDI1
Forcing di1 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface