2 2-point controller (inverse) 31, Point controller 31 – West Control Solutions KS 42-1 User Manual
Page 31
4.4.2 2-point controller (inverse)
ConF / Cntr: SP.Fn = 0
set-point controller
C.Fnc = 1
2-point controller (PID)
C.Act = 0
inverse action
(e.g. heating applications)
ConF / Out.1: O.Act = 0
action
Out.1 direct
Y.1
=
1
control output Y1 active
PArA / Cntr: Pb1
= 0,1...9999
proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1
= 1...9999
integral time 1 (heating) in sec.
td1
= 1...9999
derivative time 1 (heating) in sec.
t1
= 0,4...9999
min. cycle time 1 (heating)
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff
g
For direct action, the controller action must be changed
(
ConF / Cntr / C.Act = 1 ).
Configuration level
Operating KS4x-1
31
Configuration examples
InH.1
InL.1
SP.LO
SP
SP.Hi
Out.1Â
InP.1Ê
100%
0%
PB1
setpoint
output
process value