7 alarm handling 18, Alarm handling 18 - 19, 7 alarm handling – West Control Solutions KS 42-1 User Manual
Page 18: Formulas, Parameter adjustment effects, Operation
![background image](/manuals/370835/18/background.png)
The control parameters can be determined from the values calculated for delay
time T
u
, maximum rate of increase v
max
, control range X
h
and characteristic K ac-
cording to the formulas given below. Increase Xp, if line-out to the set-point os-
cillates.
3.7 Alarm handling
Max. three alarms can be configured and assigned to the individual outputs. Ge-
nerally, outputs
OuT.1... OuT.3 can be used each for alarm signalling. If more
than one signal is linked to one output the signals are OR linked. Each of the 3 li-
mit values
Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which
can be switched off individually (parameter = “
OFF”). Switching difference
HYS.x of each limit value is adjustable.
Operation
Alarm handling
18
Operating KS4x-1
Formulas
K = Vmax * Tu
controller behavior
Pb1 [phy. units]
td1 [s]
ti1 [s]
With 2-point and
3-point controllers,
the cycle time must be
adjusted to
t1 / t2 £ 0,25 * Tu
PID
1,7 * K
2 * Tu
2 * Tu
PD
0,5 * K
Tu
OFF
PI
2,6 * K
OFF
6 * Tu
P
K
OFF
OFF
3-point-stepping
1,7 * K
Tu
2 * Tu
Parameter adjustment effects
Parameter
Control
Line-out of disturbances
Start-up behaviour
Pb1 higher increased damping
slower line-out
slower reduction of duty cycle
lower
reduced damping
faster line-out
faster reduction of duty cycle
td1 higher reduced damping
faster response to disturbances faster reduction of duty cycle
lower
increased damping
slower response to disturbances slower reduction of duty cycle
ti1 higher increased damping
slower line-out
slower reduction of duty cycle
lower
reduced damping
faster line-out
faster reduction of duty cycle