4 parameters 38, Parameters 38 - 39, Cntr – West Control Solutions KS 42-1 User Manual
Page 38: Setp, Prog, 2 parameters, Parameter setting level
![background image](/manuals/370835/38/background.png)
5.2 Parameters
Parameter setting level
Operating KS4x-1
38
Parameters
Cntr
Name
Value range Description
Default
Pb1
1...9999 1
Proportional band 1/2 (heating) in phys. dimensions (e.g. °C)
100
Pb2
1...9999 1
Proportional band 2 (cooling) in phys. dimensions (e.g. °C)
100
ti1
1...9999
Integral action time 1 (heating) [s]
180
ti2
1...9999
Integral action time 2 (cooling) [s]
180
td1
1...9999
Derivative action time 1 (heating) [s]
180
td2
1...9999
Derivative action time 2 (cooling) [s]
180
t1
t2
0,4...9999
Minimal cycle duration 1/2 (heating/cooling) [s]. The minimum
impulse is 1/4 x t1/t2
10
SH
0...9999
Dead zone or switching differential for on-off control [phys.
dimensions)
2
d.SP
-1999...9999
Trigger point speration for series contact
D / Y / Off [phys.
dimensions]
100
tP
0,1...9999
Minimum impulse [s]
OFF
tt
3...9999
Actuator response time for servo-motor [s]
60
Y2
-120...120
2. correcting variable
0
Y.Lo
-120...120
Lower output limit [%]
0
Y.Hi
-120...120
Upper output limit [%]
100
Y.0
-120...120
Working point for the correcting variable [%]
0
Ym.H
-120...120
Limitation of the mean value Ym [%]
5
L.Ym
0...9999
Max. deviation xw at the start of mean value calculation [phys.
dimensions]
8
1
Valid for
ConF/ othr/ DP = 0. At DP = 1/ 2/ 3 also 0,1 / 0,01 / 0,001.
SEtP
Name
Value range Description
Default
SP.LO
-1999...9999
Set-point limit low for Weff
0
SP.Hi
-1999...9999
Set-point limit high for Weff
900
SP.2
-1999...9999
Set-point 2.
0
r.SP
0...9999
Set-point gradient [/min]
OFF
t.SP
0...9999
Timer time [min]
5
SP
-1999...9999
Set-point (only visible with BlueControl!)
0
ProG
Name
Value range Description
Default
SP.01
-1999...9999
Segment end set-point 1
100 1
Pt.01
0...9999
Segment time 1 [min]
10 2
SP.02
-1999...9999
Segment end set-point 2
100 1
Pt.02
0...9999
Segment time 2 [min]
10 2
SP.03
-1999...9999
Segment end set-point 3
200 1
Pt.03
0...9999
Segment time 3 [min]
10 2