beautypg.com

3 3-point controller (relay & relay) 32, Point controller 32 – West Control Solutions KS 42-1 User Manual

Page 32

background image

4.4.3 3-point controller (relay & relay)

ConF / Cntr: SP.Fn = 0

set-point controller

C.Fnc = 3

3-point controller (2xPID)

C.Act = 0

action inverse
(e.g. heating applications)

ConF / Out.1: O.Act = 0

action

Out.1 direct

Y.1

=

1

control output Y1 active

Y.2

=

0

control output Y2 not active

ConF / Out.2: O.Act = 0

action

Out.2 direct

Y.1

=

0

control output Y1 not active

Y.2

=

1

control output Y2 active

PArA / Cntr: Pb1

= 0,1...9999

proportional band 1 (heating)
in units of phys. quantity (e.g. °C)

Pb2

= 0,1...9999

proportional band 2 (cooling)
in units of phys. quantity (e.g. °C)

ti1

= 1...9999

integral time 1 (heating) in sec.

ti2

= 1...9999

derivative time 2 (cooling) in sec.

td1

= 1...9999

integral time 1 (heating) in sec.

td2

= 1...9999

derivative time 2 (cooling) in sec.

t1

= 0,4...9999

min. cycle time 1 (heating)

t2

= 0,4...9999

min. cycle time 2 (cooling)

SH

= 0...9999

neutr. zone in units of phys.quantity

PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff

SP.Hi = -1999...9999 set-point limit high for Weff

Configuration level

Configuration examples

32

Operating KS4x-1

InH.1

InL.1

SP.LO

SP

SP.Hi

Out.1Â

InP.1Ê

100%

0%

100%

0%

PB1

PB2

Out.2В

This manual is related to the following products: