Configuration 23, Inp.1, Inp.2 – West Control Solutions KS 42-1 User Manual
Page 23: Configuration level
Configuration level
Configuration
23
Operating KS4x-1
InP.1
Name
Value range Description
Default
S.tYP
Sensor type selection
1
0
thermocouple type L (-100...900°C) , Fe-CuNi DIN
1
thermocouple type J (-100...1200°C) , Fe-CuNi
2
thermocouple type K (-100...1350°C), NiCr-Ni
3
thermocouple type N (-100...1300°C), Nicrosil-Nisil
4
thermocouple type S (0...1760°C), PtRh-Pt10%
5
thermocouple type R (0...1760°C), PtRh-Pt13%
20
Pt100 (-200.0 ... 100,0 °C)
21
Pt100 (-200.0 ... 850,0 °C)
22
Pt1000 (-200.0 ... 200.0 °C)
23
special 0...4500 Ohm (pre-defined as KTY11-6)
30
0...20mA / 4...20mA 1
40
0...10V / 2...10V 1
S.Lin
Linearization (only at
S.tYP = 23 (KTY 11-6),
30 (0..20mA) and 40 (0..10V) adjustable)
0
0
none
1
Linearization to specification. Creation of linearization table
withBlueControl (engineering tool) possible. The
characteristic for KTY 11-6 temperature sensors is preset.
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at
CAL level)
2
2-point correction (at
CAL level)
3
Scaling (at
PArA level)
fAI1
Forcing INP1 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
InP.2
Name
Value range Description
Default
I.Fnc
Function selection of INP2
1
0
no function (subsequent input data are skipped)
1
heating current input
2
external set-point (
SP.E)
S.tYP
Sensor type selection
31
30
0...20mA / 4...20mA 1
31
0...50mA AC 1
fAI2
Forcing INP2 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface