beautypg.com

Configuration 23, Inp.1, Inp.2 – West Control Solutions KS 42-1 User Manual

Page 23: Configuration level

background image

Configuration level

Configuration

23

Operating KS4x-1

InP.1

Name

Value range Description

Default

S.tYP

Sensor type selection

1

0

thermocouple type L (-100...900°C) , Fe-CuNi DIN

1

thermocouple type J (-100...1200°C) , Fe-CuNi

2

thermocouple type K (-100...1350°C), NiCr-Ni

3

thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

thermocouple type S (0...1760°C), PtRh-Pt10%

5

thermocouple type R (0...1760°C), PtRh-Pt13%

20

Pt100 (-200.0 ... 100,0 °C)

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0 ... 200.0 °C)

23

special 0...4500 Ohm (pre-defined as KTY11-6)

30

0...20mA / 4...20mA 1

40

0...10V / 2...10V 1

S.Lin

Linearization (only at

S.tYP = 23 (KTY 11-6),

30 (0..20mA) and 40 (0..10V) adjustable)

0

0

none

1

Linearization to specification. Creation of linearization table

withBlueControl (engineering tool) possible. The

characteristic for KTY 11-6 temperature sensors is preset.

Corr

Measured value correction / scaling

0

0

Without scaling

1

Offset correction (at

CAL level)

2

2-point correction (at

CAL level)

3

Scaling (at

PArA level)

fAI1

Forcing INP1 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

InP.2

Name

Value range Description

Default

I.Fnc

Function selection of INP2

1

0

no function (subsequent input data are skipped)

1

heating current input

2

external set-point (

SP.E)

S.tYP

Sensor type selection

31

30

0...20mA / 4...20mA 1

31

0...50mA AC 1

fAI2

Forcing INP2 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

This manual is related to the following products: