Othr, Configuration level – West Control Solutions KS 42-1 User Manual
Page 28

Configuration level
Configuration
28
Operating KS4x-1
Name
Value range Description
Default
fDI2
Forcing di2 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
fDI3
Forcing di3 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
othr
Name
Value range Description
Default
bAud
Baudrate of the interface (only visible with OPTION)
2
0
2400 Baud
1
4800 Baud
2
9600 Baud
3
19200 Baud
Addr
1...247
Address on the interace (only visible with OPTION)
1
PrtY
Parity (only visible with OPTION)
1
0
no parity (2 stop bits)
1
even parity
2
odd parity
dELY
0...200
Delay of response signal [ms] (only visible with OPTION)
0
Unit
Unit
1
0
without unit
1
°C
2
°F
dP
Decimal point (max. number of digits behind the decimal
point)
0
0
no digit behind the decimal point
1
1 digit behind the decimal point
2
2 digits behind the decimal point
3
3 digits behind the decimal point
C.dEl
0..200
Modem delay [ms]
0
FrEq
Switching 50 Hz / 60 Hz (only visible with BlueControl!)
0
0
50 Hz
1
60 Hz
ICof
Block controller off (only visible with BlueControl!)
0
0
Released
1
Blocked
IAda
Block auto tuning (only visible with BlueControl!)
0
0
Released
1
Blocked
IExo
Block extended operating level (only visible with
BlueControl!)
0
0
Released
1
Blocked
Pass
OFF...9999
Password (only visible with BlueControl!)
OFF