Operation – West Control Solutions KS 42-1 User Manual
Page 13

g
Saved alarms (Err-LED is lit) can be acknowledged and deleted with the digital
input di1/2/3 or the Ò-key.
Configuration, see page 27:
ConF / LOGI / Err.r
g
If an alarm is still valid that means the cause of the alarm is not removed so far
(Err-LED blinks), then other saved alarms can not be acknowledged and deleted.
Self-tuning heating (
ADA.H) and cooling ( ADA.C) error status:
Operation
Operating KS4x-1
13
Maintenance manager / Error list
Name
Description
Cause
Possible remedial action
LooP
Control loop alarm
(LOOP)
- Input signal defective or not
connected correctly
- Output not connected
correctly
- Check heating or cooling circuit
- Check sensor and replace it, if necessary
- Check controller and switching device
AdA.H
Self-tuning heating
alarm
(ADAH)
- See Self-tuning heating error
status
- see Self-tuning heating error status
AdA.C
Self-tuning heating
alarm cooling
(ADAC)
- See Self-tuning cooling error
status
- see Self-tuning cooling error status
LiM.1
stored limit alarm 1
- adjusted limit value 1
exceeded
- check process
Lim.2
stored limit alarm 2
- adjusted limit value 2
exceeded
- check process
Lim.3
stored limit alarm 3
- adjusted limit value 3
exceeded
- check process
Inf.1
time limit value
message
- adjusted number of operating
hours reached
- application-specific
Inf.2
duty cycle message
(digital ouputs)
- adjusted number of duty
cycles reached
- application-specific
Error status
Description
Behaviour
0
No error
3
Faulty control action
Re-configure controller (inverse i direct)
4
No response of process
variable
The control loop is perhaps not closed: check sensor,
connections and process
5
Low reversal point
Increase (
ADA.H) max. output limiting Y.Hi or
decrease (
ADA.C) min. output limiting Y.Lo
6
Danger of exceeded set-point
(parameter determined)
If necessary, increase (inverse) or reduce (direct) set-point
7
Output step change too small
(dy > 5%)
Increase (
ADA.H) max. output limiting Y.Hi or reduce
(
ADA.C) min. output limiting Y.Lo
8
Set-point reserve too small
Increase set-point (invers), reduce set-point (direct)
or increase set-point range
(r
PArA / SEtp / SP.LO and SP.Hi )