Section 4.4

Part B IFC 040 Signal converter

ALTOFLUX 2W

02/2001

30

Display texts

Description and settings

FCt. 3.4

APPLICATION

Application = set characteristic of measuring point

inFo

emPtY PiPe

Pipe/tube has run dry

Edit

YES

NO

Standard: Yes

The empty pipe identifier can be switched on (YES) and off
(NO). A load-independent current of approx. 25nA flows
continuously from the electrodes to ground (pipeline /
grounding rings). If this current can no longer flow, and the
empty pipe identifier is activated, the measured value is set to
zero and an error message is enabled (see Fct. 1.4, setting of
“Display messages"). If not required, deactivate the empty
pipe identifier (=NO).

inFo

Field current

Field current
Default value for maximum allowable field current.

Edit

100-50-25mA

50-25mA

25mA

Standard: 100-50-25mA

If the available energy is not sufficient for the set maximum
field current, automatic reduction to the next lower value.
Where flow is pulsating, it is advised to reduce the field
current from 100mA

pp

(setting: 100-50-25mA) to 50mA

pp

(setting: 50-25mA). Above approx. 10-20% flow, continuous
measurement is then present.

inFo

ModuS F.current

F current mode

Edit

two timeS

three timeS

Standard: two times

The double setting is standard

(follows flow at a faster rate),

The triple setting reduces strong interference

(e.g. from solids contents).

inFo

limit

Limitation

Edit

150 Perc.
300 Perc.

1000 Perc.

Standard: 150 %

1

150% setting is standard,

2

300% and 1000% settings (advisable with pulsating flow
or low conductivity),

all as percentage of full-scale value, see Fct. 1.1.

Please note:
3

if noise filter used (see following function), set limitation
to 1000%.

4

Do not increase limitation if process liquids contain
solids.

inFo

Filter

Filter

Edit

Filter off

PulSe Filter

noiSe Filter

Standard: filter off

Filter ‘off’ setting is standard,

Noise filter if conductivity is low

(for characteristic, see Fig. 6 in Section 2.3)

Activate pulse filter if solids contents or other pulsed
interference involved
(for characteristic see Fig. 7 in Section 2.3).

Please note:
Further settings are required when pulse filter or noise filter is
activated, see below: