Section 4.4

Part B IFC 040 Signal converter

ALTOFLUX 2W

02/2001

28

Display texts

Description and settings

FCt. 3.1

LANGUAGE

Select language for display texts

Edit

EnGliSh

French

German

Standard: English

FCt. 3.2

FLOW METER

Primary head – to set data
Data have been factory-set. Changes here only necessary
when the electronic unit has been replaced.

inFo

diameter

Meter size (nominal diameter)

XXX.X

mm

Range

10 - 250 mm =

3

/

8

“ - 6“

Standard: see nameplate

Set nominal diameter / meter size of the primary head
(flowmeter). DN 150 / 6” is currently the largest size
available.

inFo

Full Scale

Full-scale range

XXX.XXX

m3/h

l/s

Ga./m

"user unit"

Range:

0.3-12 m/s = 1-40 ft/

s

Set full-scale range, i.e. the maximum occurring flow. This
affects all functions in which values have to be set as % of
the full-scale range:

Fct. 1.3 Low-flow cutoff

Fct. 1.5 Current output

Fct. 1.7 Status output

Fct. 2.1 Test Q

Fct. 3.4 Application

inFo

PrimarY conStant

Primary constant

XX.XXXX

GKL

Range 1.0 ... 19.9999

Standard: see nameplate

The primary constant is used for setting three calibration
values for the primary head.

GKL describes the calibration value at 100mA

pp

field current

(see nameplate).

X.XXXX

K50

Range 0.5 ... 1,5

Standard: see nameplate

K50 describes the variation at 50mA

pp

field current compared

to 100mA

pp

(see nameplate).

X.XXXX

K25

Range 0.5 ... 1.5

Standard: see nameplate

K25 describes the variation at 25mA

pp

field current compared

to 100mA

pp

(see nameplate).

inFo

Flow direction

Define direction of flow
according to direction shown by arrow on the primary head

Edit

PoS. Flow

neG. Flow

Standard: pos. flow

Set the main direction of flow or
the forward flow in the case of F/R mode:
in direction of arrow

=

PoS. DFl. (positive flow)

opposite dir. of arrow

=

neG. DFl. (negative flow)