Section 4.4

Part B IFC 040 Signal converter

ALTOFLUX 2W

02/2001

26

Display texts

Description and settings

FCt. 1.7

STATUS OUTPUT

Status output
Settings for the status output

Only possible when “Status output” set under Fct. 3.5
Hardware.
When “Pulse output” selected, Fct. 1.7 has “no function".

inFo

Function

Edit

off
on

all error

SiGn

overflow

emPtY PiPe

auto.ranGe

(für Stromausgang)

limit value

Standard: off

Setting the characteristic of the pulse output

Switch open

Switch closed

permanently

-

-

permanently

error

no error

positive flow

negative flow

no overranging

overranging

pipe/tube completely filled

pipe/tube empty

range above limit

range below limit

normal function

zoom-in function active

inactive

active

inFo

limit

XXX

Perc.

Range 5 ... 80%

Standard: 20%

When automatic range change selected
the limit value must be set as a percentage of the full-scale
range (Q

100%

), (see Fct. 1.1):

Below the set limit value, the current output has a zoom-in
function. The flow range from “0” to “Limit” is projected to the
I

0%

to I

100%

range.

For characteristic of automatic range change, see Fig. 4 in
Section 2.3

inFo

1.limit.value

XXX

Perc.

Range 0.1 ... 110 %

Standard: 10 %

inFo

2.limit.value

XXX

Perc.

Range 0.1 ... 110 %

Standard: 20 %

When limit value selected
the ‘on’ and ‘off’ values must be set as a percentage of the
full-scale range (Q

100%

) (see Fct. 1.1):

with adjustable hysteresis, as the ‘on’ value can be smaller or
larger than the ‘off’ value.

For characteristic of limit switch, see Fig. 5 in Section 2.3