6.6 Sequence for setting parameters (example)

The following description refers to a storage tank. If the device no longer contains the default
parameters, the keystroke combination for entering the numerical values may differ.

INFORMATION!
Only for version with local display valid.

Activity

Keys to be
actuated

Content of display after
activity

Entry into configuration menu

Fct. 1.0

Operation

Setting the parameter: tank height

↑↑→→

Fct. 3.1.1

Tank Height

Display of default value

10.000 m

Input of tank height "5.30 m"

→↓→5x↑→3x↑

05.300 m

Confirm tank height and move to block distance ^↑

Fct. 3.1.2

Block Dist.

Display default value

0.5000 m

Enter block distance "0.60 m"

→↑

0.6000 m

Confirm block distance and move to current

output configuration

^^↑↑

Fct. 3.3

Signal Outp.

Move to lower range value

→↑↑

Fct. 3.3.3

Scale 4 mA

Display default value

+ 00.000 m

Enter lower range value (0.4 m = 4 mA)

3x→4x↑

+ 00.400 m

Confirm lower range value and move to full-

scale range value

^↑

Fct. 3.3.4

Scale 20 mA

Display default value

010.00 m

Enter full-scale value (4.0 m = 20 mA)

2x→↓→4x↑

004.00 m

Confirm full-scale value and move to empty

tank spectrum

^^↑↑→↑

Fct. 3.5.2

Empty Spect.

Select: re-record empty spectrum

→↑↑

Record

Store changed parameters

^

Store Yes

Confirm and select: averaging

^↑

Average

Confirm and start recording; then wait for

approx. 1...3 minutes!

^^

Ready

Confirm and move to tank type

^7x↑

Fct. 3.5.9

Tanktype

Display of default value

Process Tank

Select tank type "storage tank"

↑↑

Storage Tank

Return to measurement function with

confirmation of changed parameters

5x^

Starting, then meas.val. display