4

ELECTRICAL CONNECTIONS

30

BM 702 A

www.krohne.com

09/2009 - 4000643301 - MA BM 702 A R01 en

4.2.2 Non-Ex

4.2.3 Ex i

Figure 4-2: Electrical connections for non-Ex devices

1 Power supply
2 Resistor for HART

®

communication

3 14.5...30 VDC for an output of 22 mA at the terminal

Figure 4-3: HART

®

connection to the Ex i circuit with a resistor

1 Intrinsically-safe power supply
2 Zone non-Ex
3 Zone Ex
4 Resistor for HART

®

communication

5 14.5...30 VDC for an output of 22 mA at the terminal

INFORMATION!
If the barrier has a HART

®

terminal, you can connect HART

®

devices directly to the barrier

without a resistor.

Figure 4-4: HART

®

connection to the Ex i barrier without a resistor

1 Intrinsically-safe power supply
2 Zone non-Ex
3 Zone Ex
4 14.5...30 VDC for an output of 22 mA at the terminal

.book Page 30 Thursday, September 3, 2009 2:53 PM